2008-04-03 07:55:56 | |
| BUILDING PLAN REVIEW |
| PERMIT: 08030674 |
| ADD: 2000 PRESIDENTIAL WAY #1201 |
| CONT: CATEGORY 5 HURRICANE SHUTTERS |
| TEL: (561)620-9152 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST 4-2-08 |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)THE DESIGN PRESSURES SUBMITTED SEEMS LOW FOR THE |
| HEIGHT OF THE BUILDING. WHEN USING THE DESIGN PRESSURES |
| FROM TABLE 1609.6.2.1(2) AND TABLE 1609.6.2.1(4) FOR |
| EXPOSURE {C} FOR BUILDINGS 60 FEET IN HEIGHT, THE |
| DESIGN PRESSURES ARE FAIRLY CLOSE TO THE PRESSURES |
| SUBMITTED FOR A BUILDING WITH A MEAN ROOF HEIGHT OF 188 |
| FEET. ON THE CALCULATION SHEET, STATE WHAT METHOD IS |
| BEING USED TO ACHIEVE THE DESIGN PRESSURES. |
| |
| 3)FBC 1609.1.1 |
| WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| DETERMINED IN ACCORDANCE WITH SECTION 6 OF ASCE 7. WIND |
| SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION |
| AND WIND PRESSURES SHALL BE ASSUMED TO ACT NORMAL TO |
| THE SURFACE CONSIDERED. THE ENGINEER SHALL STATE |
| HIS/HER DESIGN CRITERIA ON EACH CALCULATION SHEETS. THE |
| SHEETS SUBMITTED DOES NOT STATE THIS INFORMATION. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |