2008-04-03 14:00:03***DENIED***
  
 1) A PRELIMINARY FIELD VISIT FROM THIS OFFICE REVEALED
 THE POSSIBILITY THAT THIS CURRENT SYSTEM IS NOT BEING
 MONITORED. SUBMITTED MANUFACTURER SPECIFICATIONS
 INDICATE AN OPTIONAL DACT/DIALER AND ON OTHER PAPERWORK
 A COMMUNICATOR FOR THIS SYSTEM, BUT THIS ARRANGEMENT IS
 NOT SHOWN ON THE RISER DIAGRAM FOR VERIFICATION. PLEASE
 ADD APPROPRIATE INFORMATION TO PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW