Plan Review Notes For Permit 08030648 |
Permit Number |
08030648 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-08 10:34:46 | *****DENIED***** | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 3.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED | | DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND | | AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN | | PLACE AND CONTINUOUSLY MAINTAINED. | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 5.AMEND FIRE EXTINGUISHER VERBAGE TO READ 2A10BC | | INSTEAD OF WHAT IS INDICATED IN GENERAL NOTES #5 ON | | SHEET A1.0 | | | | 6.THE CODE SUMMARY INFORMATION ON SHEET A1.0 STATES | | THAT THERE IS ONLY ONE FLOOR, HOWEVER, A SECOND FLOOR | | IS SHOWN ON SHEET E2.PLEASE EXPLAIN. | | | | 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR | | THE PROPOSED SCOPE OF WORK.SHOW THE LOCATION OF THE | | FIRE ALARM DEVICES FOR THE PROPOSED SCOPE OF WORK. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|