Date |
Text |
2008-06-02 15:35:43 | ** DENIEDRESUB** |
| |
| |
| 1) NOTE: PLANS/RISER NOW CLEARLY INDICATES THE LOCATION |
| OF ALL EQUIPMENT ON ELECTRICAL SHEETS HOWEVER PLEASE |
| SEE SITE PLANS AS THE SERVICE IS STILL SHOWN IN TWO |
| COMPLETELY DIFFERENT LOCATIONS. PLEASE ALSO SEE THAT |
| THE ATS PANEL IS NOT SHOWN ON SITE PLANS. THE |
| ELECTRICAL RISER ONLY NOW MENTIONS THIS IS BEING |
| PROPOSED TO BE LOCATED INSIDE A WEATHER PROOF JUNCTION |
| BOX WHICH IS NOT PERMITTED. THIS ENCLOSURE SHALL BE |
| NEMA 3R IF ITS GOING TO BE INSTALLED OUTSIDE. |
| IT IS NOT PERMITTED INSIDE A NEMA 3R JUNCTION BOX. |
| 110.3, 90.7 |
| |
| 2) NOTE: PLEASE KNOW AS INFORMED BEFORE PLANS WERE |
| RESUBMITTED THE GENERATOR SHALL BE APPLIED FOR BY A |
| LICENSED CONTRACTOR MEETING ALL LICENSE REQUIREMENTS OF |
| FLORIDA STATUTES 527.02. THIS IS ENFORCED BY THE STATE |
| OF FLORIDA CONTRACTORS LICENSING BOARD ALONG WITH THE |
| DEPARTMENT OF AGRICULTURE. |
| PLEASE OBTAIN LICENSING OR PLEASE FILE FOR CHANGE IN |
| CONTRACTOR FOR THE LICENSED GAS CONTRACTOR TO BE THE |
| PRIME PERMIT HOLDER OF PROJECT. |
| THIS IS NOT A NEW STATUTE HOWEVER THIS OFFICE HAS BEEN |
| GIVEN NOTICE BY THE STATE THAT THE ELECTRICAL |
| CONTRACTOR MAY NOT INSTALL, SELL GAS GENERATOR |
| APPLIANCES EVEN IF THE GAS CONNECTION IS DONE BY A |
| LICENSED GAS/LP CONTRACTOR. |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |