Plan Review Notes
Plan Review Notes For Permit 08030561
Permit Number 08030561
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-02 15:35:43** DENIEDRESUB**
  
  
 1) NOTE: PLANS/RISER NOW CLEARLY INDICATES THE LOCATION
 OF ALL EQUIPMENT ON ELECTRICAL SHEETS HOWEVER PLEASE
 SEE SITE PLANS AS THE SERVICE IS STILL SHOWN IN TWO
 COMPLETELY DIFFERENT LOCATIONS. PLEASE ALSO SEE THAT
 THE ATS PANEL IS NOT SHOWN ON SITE PLANS. THE
 ELECTRICAL RISER ONLY NOW MENTIONS THIS IS BEING
 PROPOSED TO BE LOCATED INSIDE A WEATHER PROOF JUNCTION
 BOX WHICH IS NOT PERMITTED. THIS ENCLOSURE SHALL BE
 NEMA 3R IF ITS GOING TO BE INSTALLED OUTSIDE.
 IT IS NOT PERMITTED INSIDE A NEMA 3R JUNCTION BOX.
 110.3, 90.7
  
 2) NOTE: PLEASE KNOW AS INFORMED BEFORE PLANS WERE
 RESUBMITTED THE GENERATOR SHALL BE APPLIED FOR BY A
 LICENSED CONTRACTOR MEETING ALL LICENSE REQUIREMENTS OF
 FLORIDA STATUTES 527.02. THIS IS ENFORCED BY THE STATE
 OF FLORIDA CONTRACTORS LICENSING BOARD ALONG WITH THE
 DEPARTMENT OF AGRICULTURE.
 PLEASE OBTAIN LICENSING OR PLEASE FILE FOR CHANGE IN
 CONTRACTOR FOR THE LICENSED GAS CONTRACTOR TO BE THE
 PRIME PERMIT HOLDER OF PROJECT.
 THIS IS NOT A NEW STATUTE HOWEVER THIS OFFICE HAS BEEN
 GIVEN NOTICE BY THE STATE THAT THE ELECTRICAL
 CONTRACTOR MAY NOT INSTALL, SELL GAS GENERATOR
 APPLIANCES EVEN IF THE GAS CONNECTION IS DONE BY A
 LICENSED GAS/LP CONTRACTOR.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  