2008-04-02 10:52:17 | ** DENIED** |
| |
| 1) NOTE: PLEASE CORRELATE PLANS WITH THE ELECTRICAL |
| RISER DIAGRAM. THE SITE/SURVEY PLANS SHOWS THE PANEL |
| BEING INSTALLED OUTSIDE YET THE RISER SHOWS THE MAIN |
| PANEL INSIDE. WHICH ONE IS IT? |
| 225.24, 230.72, 110.26, 240.24 ETC |
| |
| 2) NOTE: PLEASE KNOW THAT THE COPY OF THE GENERATOR |
| CHECKLIST BEING SUBMITTED WAS A ROUGH DRAFT OF 2006 AND |
| NOT A FINAL DOCUMENT. |
| |
| 3) NOTE: PLEASE SEE THE ACTUAL LOADS ON THIS NEW SUB |
| PANEL MAY NOT BE DE-RATED FOR HEATING. THE HEATING LOAD |
| IS TO BE DONE AT 100% UNLESS LOAD SHEDDING IS PROVIDED. |
| |
| PLEASE ADJUST CALCULATIONS OR HOW SYSTEM WILL BE |
| INSTALLED. |
| PLEASE ALSO ONLY SUBMIT LOADS FOR SUB PANEL. THE |
| EXISTING SERVICE LOAD IS NOT NEEDED. |
| PLEASE SUBMIT A PANEL SCHEDULE FOR NEW INTENDED |
| CIRCUITS COMPLETE WITH WIRE SIZE AND THE SIZE OF THE |
| OCP/BREAKER FOR CIRCUIT. |
| 220, 702.5, 240.4, 310.16, 408.4 |
| FBC 106.1.2, 106.3.5.4 |
| |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |