2008-03-25 14:45:192004 FBC W/2007 REVISIONS
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE C, HOWEVER THE
 DESIGN PRESSURE CALCULATION IS FOR EXPOSURE B. REVISE
 THE OPENING WIND LOAD PRESSURES. SEE FBC R301.2.1.4 AND
 TABLE 301.2(2).
  
 2) NOTE: THE LOCATION OF THE OPENING IS IN THE INTERIOR
 ZONE NOT THE END ZONE AS SPECIFIED ON THE CALCULATION.
  
  
 3) SPECIFY THE HEADER TYPE AND LENGTH ON SCHEDULE 'J'
 PAGES 13 AND 14 OF DRAWINGS. FBC 106.1.1* CITY
 AMENDMENTS
  