 BUILDING PLAN REVIEW
 PERMIT: 08030531
 ADD: 2000 PRESIDENTIAL WAY #1005
 CONT: STORM FORCE SHUTTERS
 TEL: (561)745-7889
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)PER 1609.6.1 THE SIMPLIFIED CALCULATION METHOD FOR
 WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FEET IN HEIGHT. PLEASE
 SUBMIT SIGNED AND SEALED ENGINEERS? CALCULATION FOR THE
 WIND PRESSURES. ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH SHEET THAT
 BEARS THEIR SEAL PER FAC 61G15-23.002
  