Plan Review Notes For Permit 08030526 |
Permit Number |
08030526 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-04-22 11:59:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.THE NOA SUBMITTED IS EXPIRED8/22/07); PLEASE | | PROVIDE TWO SETS OF THE CURRENT EVALUATION REPORT. | | FAC9B72.THIS MAY BE AVAILABLE AT | | WWW.BUILDINGCODEONLINE.COM | | | | 2.SEE PAGE 7 OF THE NOA SUBMITTED.INSULATION | | FASTENER IS TO BE IN ACCORDANCE WITH FASTENER DENSITY | | FOR THE SYSTEM; THE ASSEMBLY YOU HAVE SELECTED | | SPECIFIES 1:4 SF, SO A 4X8 SHEET WOULD REQUIRE 8 | | FASTENERS.ON SHEET 10, YOU'VE INDICATED THAT THE | | FIELD WOULD BE INSTALLED WITH 4 FASTENERS.PERIMETER | | AND CORNER FASTENING IS ALSO NOT COMPLIANT WITH THE NOA | | AND RAS117.PLEASE RESOLVE THIS PRIOR TO RESUBMITTAL. | | | | | | 3.PLEASE REVISE THE OWNER ON EACH PERMIT APPLICATION | | TO REFECT THE CURRENT OWNER.I HAVE PRINTED PAPA | | RECORDS FOR EACH UNIT FOR YOUR REFERENCE. |
|