Plan Review Notes
Plan Review Notes For Permit 08030500
Permit Number 08030500
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-11 14:07:06REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG AC-1: GENERAL NOTE #2 CALLS FOR RETURN DUCT TO BE
 TIGHT TO UNDERSIDE OF SUPPLY DUCT. SUFFICIENT SPACE
 SHALL BE PROVIDED ADJACENT TO ALL MECHANICAL COMPONENTS
 LOCATED IN OR FORMING A PART OF THE AIR DISTRIBUTION
 SYSTEM TO ASSURE ADEQUATE ACCESS FOR (1) CONSTRUCTION
 AND SEALING IN ACCORDANCE WITH THE REQUIREMENTS OF
 SECTION 603.1 OF THIS CODE; (2) INSPECTION; AND (3)
 CLEANING AND MAINTENANCE IN ACCORDANCE WITH FBCM
 603.1.3. SHOW HOW THIS IS TO BE ACCOMPLISHED WITH THESE
 TWO DUCT SYSTEMS TIGHT TO EACH OTHER.
  
 2. PG AC-2: GENERAL NOTES #1 INDICATES THAT EF-1 AND
 EF-2 ARE TO BE LOCATED ON ROOF ABOVE THE GARAGE, BUT
 THE GARAGE VENTILATION PLAN AND THE FAN SCHEDULE CALL
 FOR EF-7 AND EF-8 TO BE FOR THE GARAGE. PLEASE
 COORDINATE PLANS, SCHEDULES AND NOTES TO CLARIFY THE
 SCOPE OF WORK. FBCM 401.1 AND FBCB 106.1.1.
  
 3. PG AC-2: PLEASE INDICATE ON PLANS THE SOURCE OF
 MAKEUP AIR FOR EF-7 IN GARAGE. PLAN INDICATES SF-1 WILL
 ONLY OPERATE DURING CO ALARM MODE IN CONJUNCTION WITH
 EF-8.
  
 4. PG AC-2: PLEASE INDICATE ON PLANS WHICH METHOD WAS
 USED FOR DESIGN OF THE VENTILATION (OUTDOOR AIR). ONE
 OF TWO METHODS SHALL BE SELECTED IN ACCORDANCE WITH
 FBCM 403.1 AND 403.4. IT APPEARS THAT TABLE 403.3 WAS
 USED. HOWEVER, THERE ARE SOME CALCULATIONS WHICH DO NOT
 CORRESPOND WITH THE TABLE. EXAMPLE: THE RECEPTION AREA
 IS SHOWN AS BEING 465 SQUARE FEET. THE TABLE PUTS THE
 OCCUPANT LOAD AT 60 PEOPLE PER 1000SF FOR A TOTAL
 OCCUPANT LOAD OF 28 PEOPLE. THE TABLE ALSO CALLS FOR A
 VENTILATION RATE OF 15CFM PER PERSON. THIS GIVES A
 REQUIREMENT OF 420CFM OF OUTDOOR AIR FOR THIS AREA.
 THERE ARE OTHER AREAS WHICH APPEAR TO BE MISCALCULATED.
 PLEASE VERIFY ALL VALUES ON THE OUTDOOR AIR SUMMARY
 PRIOR TO RESUBMITTAL.
  
  
 5. PG AC-2: AIR CONDITIONING CONTROL SEQUENCE NOTE #4
 CALLS FOR EXHAUST FANS TO BE INTERLOCKED WITH ROOM
 LIGHT SWITCHES. WHERE MECHANICAL EXHAUST IS REQUIRED BY
 TABLE 403.3, RECIRCULATION OF AIR FROM SUCH SPACES
 SHALL BE PROHIBITED. ALL AIR SUPPLIED TO SUCH SPACES
 SHALL BE EXHAUSTED, INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3 IN ACCORDANCE WITH FBCM
 403.2.1(3). SINCE NOTE #1 REQUIRES SUPPLY FANS TO RUN
 CONTINUOUS DURING OCCUPIED MODE, HOW WILL THE AIR BEING
 SUPPLIED TO THE TOILET ROOMS BE EXHAUSTED WHEN LIGHT
 SWITCHES ARE TURNED OFF? SHOW COMPLIANCE WITH THIS
 SECTION BY EITHER INTERLOCKING EXHAUST FANS WITH AHU?S
 OR USING TRANSFER DUCTS FOR MAKEUP AIR TO THESE ROOMS.
  
 6. PG AC-2: PLAN SHOWS FOUR CONDENSING UNITS ON ROOF.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM 301.13.
 ALSO, CLEARANCES FOR ROOFTOP EQUIPMENT AND APPLIANCES
 SHALL BE IN ACCORDANCE WITH FBCB 1509.7. PROVIDE DETAIL
 FOR ROOF CURBS OR PRODUCT APPROVAL FOR PRE-ENGINEERED
 A/C STANDS AS APPROPRIATE FOR THE INSTALLATION METHOD
 CHOSEN. IF OTHER THAN A PRE-ENGINEERED SYSTEM IS USED,
 PROVIDE WIND LOAD CALCULATIONS WITH CORRESPONDING
 ATTACHMENT DETAILS.
  
 7. ENERGY CALCULATIONS: THERE ARE SOME BUILDING
 ENVELOPE COMPONENTS IN THE INPUT DATA REPORT (IDR)
 WHICH DO NOT CORRESPOND WITH THE INFORMATION ON THE
 PLANS. EXAMPLE: THERE ARE NO DOORS SHOWN IN THE IDR
 WHILE THE ARCHITECTURAL FLOOR PLAN SHOWS NEW DOORS
 BEING INSTALLED. EXAMPLE: THE IDR CALLS FOR R-22.2 ON
 THE ROOF, INCLUDING R-19 MINERAL WOOL BATTS.
 ARCHITECTURAL PLANS DO NOT CALL FOR R-19 BATTS. PLEASE
 SHOW ON PLANS HOW THE R-22.2 IS TO BE ACHIEVED OR
 ADJUST CALCULATIONS TO THE R-VALUE OF THE EXISTING ROOF
 SYSTEM PLUS THE INSULATION BEING ADDED AS SHOWN ON
 REFLECTIVE CEILING PLAN. THE OWNER SHALL DEMONSTRATE TO
 THE BUILDING DEPARTMENT?S SATISFACTION THAT ALL
 R-VALUES AND EQUIPMENT EFFICIENCIES CLAIMED ARE
 PRESENT. IF THE BUILDING WAS BUILT AFTER 1980, THE
 ORIGINAL ENERGY CODE SUBMITTAL MAY BE USED TO
 DEMONSTRATE EFFICIENCIES IN ACCORDANCE WITH FBCB
 13-101.4.2.1.
  
 8. PG A2.3 SHOWS SKYLIGHTS WHICH MAY OR MAY NOT REMAIN.
 IS THE HEAT GAIN FROM THE SKYLIGHTS INCLUDED IN THE
 COOLING LOAD CALCULATIONS FOR A/C SIZING? DO THESE
 SKYLIGHTS HAVE AN IMPACT ON THE R-VALUE OF THE ROOF
 SYSTEM? PLEASE CLARIFY AND INDICATE WHETHER OR NOT
 THESE SKYLIGHTS WILL REMAIN. THE PLANS AND
 SPECIFICATIONS, INCLUDING THE ENERGY CODE CALCULATIONS,
 SHALL SHOW, IN SUFFICIENT DETAIL, ALL PERTINENT DATA
 AND FEATURES OF THE BUILDING IN ACCORDANCE WITH FBCB
 13-103.2.
  