Plan Review Notes
Plan Review Notes For Permit 08030500
Permit Number 08030500
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-03 12:01:45 
2008-04-14 07:19:47BUILDING PLAN REVIEW
 PERMIT: 08030500
 ADD: 915 N DIXIE HW
 CONT: GLACE & CO
 TEL: (561)585-5564
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) PLEASE SEE AERIAL VIEW,SEE ATTACHMENT. IT APPEARS
 THAT THE WORK IS TRANGRESSING THE PROPERTY LINE AND THE
 WRONG PROPERTY CONTROL NUMBER LISTED ON THE PERMIT
 APPLICATION.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3) PLEASE PROVIDE A SITE PLAN OF THE WHOLE BUIULDING
 SITE WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 THE LEVEL OF ALTERATION UNDER THE 2004 EXISTING
 BUILDING CODE.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) NUMBER OF FLOORS
 I ) SQ. FT. FOOTPRINT, FOOTPRINT
  
 4) PLANS INDICATE A MEZZANINE, PLEASE PROVIDE AREA
 CALCULATIONS AS PER THE DEFINITION OF A MEZZANINE.
 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED
 ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH
 THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING
 THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. PLEASE
 INDICATE WHAT AREAS OFT THE MEZZANINE ARE COMMUNICATING
 WITH OTHER ROOMS.
  
 5) ADDITIONAL INFORMATION REQUIRED, THE ELECTRICAL
 REVIEWERS COMMENET# 7IS NOT LIMITED TO BUT WILL
 INCLUDE THE IT ROOM FOUND ON SHEET A2.2. THIS ROOM IS
 NOT LISTED AS A IT ROOM ON E2.2.
 IF THIS IS A TRUE USE IT ROOM THIS COMMENT WILL APPEAR
 UNDER THE ELECTRICAL REVIEWERS COMMENTS NEXT REVIEW. IT
 ROOMS ARE REQUIRED BY NFPA 645.1-4 TO HAVE CERTAIN
 RATINGS. ONE THAT WILL PERTAIN TO BUILDING IS RATED
 WALLS, OPENING PROTECTION AND THROUGH WALL PENETRATIONS
 AND HORIZONTAL PENETRATIONS, TABLE 715.3, 712.3.1 &
 712.4.1.PLEASE PROVIDE ADDITIONAL INFORMATION
 ACCORDINGLY.
 THANK YOU.
  
 6) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 ELEVATOR, MINIMUM CAR PLAN DIMENSIONS,
 11-4.1.6(2)(3)(C) ELEVATORS (I)-(III).
  
 7)SHEET A2.1 INDICATES A WALL TYPE 11 THAT SEPERATES
 THE OFFICE AREA FROM AN ENCLOSED PARKING GARAGE. THIS
 WILL REQUIRE A 2HR SEPERATION AS PER TABLE 302.3.2.
 WHERE AS THE WALL TYPE 11 IS INDICATED AS A INTERIOR
 NONRATED WALL. PLEASE INDICATE WHERE THE 2 HR FIRE
 RATED WALL WILL BE. ALSO OPENING PROTECTION TABLE
 715.3.
  
 8) REAR OF BUILDING, DOOR 111D & 111E, THE DOOR
 SCHEDULE INDICATES EACH OF THESE DOORS AS A PAIR OF
 BI-PASS DOOR WITH A CLEAR OPENING OF 2'-6", 11-4.13.5
 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM
 CLEAR WIDTH OF 32" WITH THE DOOR OPEN 90-DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND OPPOSITE
 STOP.
  
 9) PLEASE PROVIDE INFORMATION WHY RESTROOMS 109 AND 110
 ARE NOT ACCESSIBLE? IF EXISTING PLEASE PROVIDE
 CALCULATIONS FOR DISPROPORTIONATE COST11-4.1.6(2)(A).
  
 10)IS THIS A CHANGE IN OCCUPANCY ENACTING IMPACT
 FEES?BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)