2008-04-14 07:19:47 | BUILDING PLAN REVIEW |
| PERMIT: 08030500 |
| ADD: 915 N DIXIE HW |
| CONT: GLACE & CO |
| TEL: (561)585-5564 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| |
| 2) PLEASE SEE AERIAL VIEW,SEE ATTACHMENT. IT APPEARS |
| THAT THE WORK IS TRANGRESSING THE PROPERTY LINE AND THE |
| WRONG PROPERTY CONTROL NUMBER LISTED ON THE PERMIT |
| APPLICATION. |
| UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE' |
| SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 3) PLEASE PROVIDE A SITE PLAN OF THE WHOLE BUIULDING |
| SITE WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT. |
| 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. |
| THE LEVEL OF ALTERATION UNDER THE 2004 EXISTING |
| BUILDING CODE. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) |
| WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| H) NUMBER OF FLOORS |
| I ) SQ. FT. FOOTPRINT, FOOTPRINT |
| |
| 4) PLANS INDICATE A MEZZANINE, PLEASE PROVIDE AREA |
| CALCULATIONS AS PER THE DEFINITION OF A MEZZANINE. |
| 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A |
| MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED |
| ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH |
| THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL |
| NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE |
| ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING |
| THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE |
| SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. PLEASE |
| INDICATE WHAT AREAS OFT THE MEZZANINE ARE COMMUNICATING |
| WITH OTHER ROOMS. |
| |
| 5) ADDITIONAL INFORMATION REQUIRED, THE ELECTRICAL |
| REVIEWERS COMMENET# 7IS NOT LIMITED TO BUT WILL |
| INCLUDE THE IT ROOM FOUND ON SHEET A2.2. THIS ROOM IS |
| NOT LISTED AS A IT ROOM ON E2.2. |
| IF THIS IS A TRUE USE IT ROOM THIS COMMENT WILL APPEAR |
| UNDER THE ELECTRICAL REVIEWERS COMMENTS NEXT REVIEW. IT |
| ROOMS ARE REQUIRED BY NFPA 645.1-4 TO HAVE CERTAIN |
| RATINGS. ONE THAT WILL PERTAIN TO BUILDING IS RATED |
| WALLS, OPENING PROTECTION AND THROUGH WALL PENETRATIONS |
| AND HORIZONTAL PENETRATIONS, TABLE 715.3, 712.3.1 & |
| 712.4.1.PLEASE PROVIDE ADDITIONAL INFORMATION |
| ACCORDINGLY. |
| THANK YOU. |
| |
| 6) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| ELEVATOR, MINIMUM CAR PLAN DIMENSIONS, |
| 11-4.1.6(2)(3)(C) ELEVATORS (I)-(III). |
| |
| 7)SHEET A2.1 INDICATES A WALL TYPE 11 THAT SEPERATES |
| THE OFFICE AREA FROM AN ENCLOSED PARKING GARAGE. THIS |
| WILL REQUIRE A 2HR SEPERATION AS PER TABLE 302.3.2. |
| WHERE AS THE WALL TYPE 11 IS INDICATED AS A INTERIOR |
| NONRATED WALL. PLEASE INDICATE WHERE THE 2 HR FIRE |
| RATED WALL WILL BE. ALSO OPENING PROTECTION TABLE |
| 715.3. |
| |
| 8) REAR OF BUILDING, DOOR 111D & 111E, THE DOOR |
| SCHEDULE INDICATES EACH OF THESE DOORS AS A PAIR OF |
| BI-PASS DOOR WITH A CLEAR OPENING OF 2'-6", 11-4.13.5 |
| DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM |
| CLEAR WIDTH OF 32" WITH THE DOOR OPEN 90-DEGREES, |
| MEASURED BETWEEN THE FACE OF THE DOOR AND OPPOSITE |
| STOP. |
| |
| 9) PLEASE PROVIDE INFORMATION WHY RESTROOMS 109 AND 110 |
| ARE NOT ACCESSIBLE? IF EXISTING PLEASE PROVIDE |
| CALCULATIONS FOR DISPROPORTIONATE COST11-4.1.6(2)(A). |
| |
| 10)IS THIS A CHANGE IN OCCUPANCY ENACTING IMPACT |
| FEES?BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE.) |