2008-04-07 14:13:04 | 1. THE ENTIRE FIRE ALARM SYSTEM SHALL BE MONITORED BY A |
| UL LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| SERVICE. |
| |
| 2. AS NOTED ON THE PLANS, SMOKE DETECTORS SHALL BE |
| INSTALLED A MINIMUM OF THREE FEET FROM AIR CONDITIONER |
| DIFFUSERS. |
| |
| 3. SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT THE TOP |
| OF THE ATRIUM ABOVE THE MONUMENTAL STAIR. A RECENT |
| FIELD VISIT INDICATED THAT THE SMOKE DETECTORS LOCATED |
| ON THE PERIMETER OF THE ATRIUM WOULD NOT ACTIVATE |
| THEREFORE SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT |
| THE TOP. |
| |
| 4. TOTAL COMPLETE SMOKE DETECTION COVERAGE AS INDICATED |
| IN CHAPTER 5, INITIATING DEVICES WITHIN NFPA 72, THE |
| NATIONAL FIRE ALARM CODE "TOTAL COVERAGE SHALL INCLUDE |
| ALL ROOMS, HALLS, STORAGE AREAS, BASEMENTS, ATTICS, |
| LOFTS, SPACES ABOVE SUSPENDED CEILINGS AND OTHER |
| SUBDIVISIONS AND ACCESSIBLE SPACES AS WELL AS THE |
| INSIDE OF ALL CLOSETS, ELEVATOR SHAFTS, ENCLOSED |
| STAIRWAYS, DUMBWAITER SHAFTS AND CHUTES". |
| |
| 5. SMOKE DETECTORS THAT ARE INSTALLED SHALL BE |
| INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE |
| ALARM CODE AND THE MANUFACTURER'S SPECIFICATIONS. |
| |
| 6. ANY FIRE ALARM DEVICE THAT IS SUBJECT TO MOISTURE |
| INTRUSION SHALL BE INSTALLED IN A WEATHERPROOF MANNER |
| TO PREVENT DAMAGE. |
| |
| 7. THE ENTIRE FIRE ALARM SYSTEM IS SUBJECT TO FIELD |
| INSPECTION AND APPROVAL. |
| |
| APPROVED PROVISO: |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4709 PHONE |
| 804-4774 |