Plan Review Notes
Plan Review Notes For Permit 08030447
Permit Number 08030447
Review Stop E
Sequence Number 2
Notes
Date Text
2008-08-12 11:48:07 
 **REDLINED PLANS**
  
 1) NOTE: THE EXISTING RISER INDICATES AN EQUIPMENT
 GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED PER 250.6,250.24.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
 2) NOTE: ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED
 THE BASE FLOOD ELEVATION (BFE).
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]