Plan Review Notes For Permit 08030447 |
Permit Number |
08030447 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-08-12 11:48:07 | | | **REDLINED PLANS** | | | | 1) NOTE: THE EXISTING RISER INDICATES AN EQUIPMENT | | GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF | | DISCONNECT WHICH IS NOT PERMITTED PER 250.6,250.24. | | THIS WOULD CREATE OBJECTIONABLE CURRENTS. | | | | 2) NOTE: ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED | | THE BASE FLOOD ELEVATION (BFE). | | | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|