2008-03-20 10:58:28 | ** DENIEDREVIEW ** |
| |
| |
| |
| 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED |
| FOR PLAN REVIEW ONLY. ONCE ALL COMMENTS HAVE BEEN |
| ADDRESSED REVIEW WILL REMAIN IN FAILED STATUS UNTIL |
| PERMIT IS APPLIED FOR. |
| |
| 2) NOTE: PLEASE INDICATE THE FOLLOWING RELEVANT CODE ON |
| ELECTRICAL. |
| 2005 NFPA-70 |
| |
| 3) NOTE: PLEASE SUBMIT INFORMATION ON CONDUIT(S) AND |
| CONDUCTORS BEING INSTALLED AND THE SIZE OF THE EXISTING |
| SERVICE. |
| 230.70, 240.4, 310.16. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 4) NOTE: FEES WERE NOT PAID AS OF THIS REVIEW. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |