2008-03-20 10:58:28** DENIEDREVIEW **
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED
 FOR PLAN REVIEW ONLY. ONCE ALL COMMENTS HAVE BEEN
 ADDRESSED REVIEW WILL REMAIN IN FAILED STATUS UNTIL
 PERMIT IS APPLIED FOR.
  
 2) NOTE: PLEASE INDICATE THE FOLLOWING RELEVANT CODE ON
 ELECTRICAL.
 2005 NFPA-70
  
 3) NOTE: PLEASE SUBMIT INFORMATION ON CONDUIT(S) AND
 CONDUCTORS BEING INSTALLED AND THE SIZE OF THE EXISTING
 SERVICE.
 230.70, 240.4, 310.16.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: FEES WERE NOT PAID AS OF THIS REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]