2008-03-24 16:15:45 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| AND OCCUPANCY LOAD ON THE PLANS. |
| PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED |
| BELOW. |
| |
| |
| A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3, |
| AND A-5 |
| |
| B} BUSSINESS (SEE SECTION 304): GROUP B |
| |
| C} EDUCATIONAL (SEE SECTION 305): GROUP E |
| |
| D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS |
| F-1 AND F-2 |
| |
| E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3, |
| H-4, AND H-5 |
| |
| F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, |
| AND I-3 |
| |
| G} MERCANTILE (SEE SECTION 309): GROUP M |
| |
| H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3 |
| AS APPLICABLE IN SECTION 101.2, AND R-4 |
| |
| I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2 |
| |
| J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP |
| U |
| |
| K} DAY CARE (SEE SECTION 313): GROUP D |
| |
| *THIS APPEARS TO BE A BUSSINESS, HOWEVER UNTIL THE |
| BUILDING CLASSIFICATION AND OCCUPANCY LOAD ARE CLEARLY |
| INDICATED ON THE RESUBMITTED PLANS A COMPLETE PLUMBNG |
| PLAN REVIEW CAN NOT BE DONE AT THIS TIME. REFERENCE FBC |
| PLUMBING TABLE 403.1 FOR MINIMUM NUMBER OF REQUIRED |
| PLUMBING FIXTURES ONCE THE BUILDING CLASSIFICATION AND |
| OCCUPANCY LOAD HAVE BEEN ESTABLISHED AND COMPLY. |
| |
| 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| 2007 REVISIONS" |
| |
| 3. PROVIDE TWO COPIES OF THE EXISTING AND PROPOSED |
| FLOOR PLAN LAYOUT MINIMUM 1/8 INCH SCALE CLEARLY |
| INDICATING ALL THE EXISTING PLUMBING FIXTURES AND |
| PROPOSED PLUMBING FIXTURES (SHAMPOO SINKS). PER |
| (W.P.B.)SECTION 106.1 SUBMITTAL DOCUMENTS AND 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. THE A.A.V. BEING INDICATED FOR THE SHAMPOO SINKS |
| CAN NOT BE USED UNLESS THERE IS AN EXISTING VENT THRU |
| THE ROOF ON THE EXISTING SANITARY SYSTEM. CLEARLY |
| INDICATE THIS REQUIRED VENT THRU ROOF. PER FBC PLUMBING |
| SECTION 917.7 VENT REQUIRED. |
| |
| 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, |
| PLUMBING: THE ISOMETRIC POTABLE WATER RISER DIAGRAM |
| DOES NOT CLEARLY INDICATE WHAT THE FIXTURES ARE **601.1 |
| SCOPE, REQUIRED FULL-OPEN VALVE LOCATIONS **606.1.1, |
| LOCATION OF THE REQUIRED BACKFLOW PREVENTER (CLEARLY |
| INDICATE IF THE REQUIRED BACKFLOW PREVENTER IS PROPOSED |
| NEW OR EXISTING) **608, THERMAL EXPANSION CONTROL FOR |
| THE NEW WATER HEATER **607.3 AND IF THE NEW WATER |
| HEATER IS GAS OR ELECTIRC **501.1 SCOPE, RELIEF VALVE |
| (CLEARLY INDICATE THE REQUIRED T & P VALVE ON PLANS) |
| **504.4, RELIEF OUTLET WASTE (CLEARLY INDICATE ON |
| PLANS) **504.6, IS A HEATER PAN REQUIRED? **504.7, IF |
| PAN IS REQUIRED COMPLY WITH **504.7.1 PAN SIZE AND |
| DRAIN AND **504.7.2 PAN DRAIN TERMINATION AND CLEARLY |
| INDICATE ON RESUBMITTED PLANS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |