Plan Review Notes
Plan Review Notes For Permit 08030422
Permit Number 08030422
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-24 16:15:45PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED
 BELOW.
  
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS
 F-1 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2,
 AND I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP
 U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 *THIS APPEARS TO BE A BUSSINESS, HOWEVER UNTIL THE
 BUILDING CLASSIFICATION AND OCCUPANCY LOAD ARE CLEARLY
 INDICATED ON THE RESUBMITTED PLANS A COMPLETE PLUMBNG
 PLAN REVIEW CAN NOT BE DONE AT THIS TIME. REFERENCE FBC
 PLUMBING TABLE 403.1 FOR MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES ONCE THE BUILDING CLASSIFICATION AND
 OCCUPANCY LOAD HAVE BEEN ESTABLISHED AND COMPLY.
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS"
  
 3. PROVIDE TWO COPIES OF THE EXISTING AND PROPOSED
 FLOOR PLAN LAYOUT MINIMUM 1/8 INCH SCALE CLEARLY
 INDICATING ALL THE EXISTING PLUMBING FIXTURES AND
 PROPOSED PLUMBING FIXTURES (SHAMPOO SINKS). PER
 (W.P.B.)SECTION 106.1 SUBMITTAL DOCUMENTS AND 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE A.A.V. BEING INDICATED FOR THE SHAMPOO SINKS
 CAN NOT BE USED UNLESS THERE IS AN EXISTING VENT THRU
 THE ROOF ON THE EXISTING SANITARY SYSTEM. CLEARLY
 INDICATE THIS REQUIRED VENT THRU ROOF. PER FBC PLUMBING
 SECTION 917.7 VENT REQUIRED.
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: THE ISOMETRIC POTABLE WATER RISER DIAGRAM
 DOES NOT CLEARLY INDICATE WHAT THE FIXTURES ARE **601.1
 SCOPE, REQUIRED FULL-OPEN VALVE LOCATIONS **606.1.1,
 LOCATION OF THE REQUIRED BACKFLOW PREVENTER (CLEARLY
 INDICATE IF THE REQUIRED BACKFLOW PREVENTER IS PROPOSED
 NEW OR EXISTING) **608, THERMAL EXPANSION CONTROL FOR
 THE NEW WATER HEATER **607.3 AND IF THE NEW WATER
 HEATER IS GAS OR ELECTIRC **501.1 SCOPE, RELIEF VALVE
 (CLEARLY INDICATE THE REQUIRED T & P VALVE ON PLANS)
 **504.4, RELIEF OUTLET WASTE (CLEARLY INDICATE ON
 PLANS) **504.6, IS A HEATER PAN REQUIRED? **504.7, IF
 PAN IS REQUIRED COMPLY WITH **504.7.1 PAN SIZE AND
 DRAIN AND **504.7.2 PAN DRAIN TERMINATION AND CLEARLY
 INDICATE ON RESUBMITTED PLANS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  