Plan Review Notes
Plan Review Notes For Permit 08030419
Permit Number 08030419
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-31 12:51:03*****UNSAT*****
  
 1.THE CORRECT ADDRESS INCLUDING THE TENANT SPACE
 NUMBER SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.6901 JOG ROAD OR 6901 OKEECHOBEE BLVD. ??
  
 2.RECTIFY THE MIXING OF JURISDICTIONS AS SHOWN IN THE
 TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.THE AHJ AT
 THIS SCOPE OF WORK SITE IS THE CITY OF WEST PALM BEACH,
 NOT PALM BEACH COUNTY.
  
 3.SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4.AS PER LOCAL CODES, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.AMEND OR ADD TO GENERAL
 ELECTRIC NOTE, SHEET E1.
  
 5.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS IN THE
 SCOPE OF WORK SITE.ANY INSTALLATION AND/OR ALTERATION
 TO THE SPRINKLER SYSTEM REQUIRES SEPERATE PLANS AND
 PERM,IT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INBCLUDE A
 RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN
 SHEET EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722