Plan Review Notes For Permit 08030419 |
Permit Number |
08030419 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-31 12:51:03 | *****UNSAT***** | | | | 1.THE CORRECT ADDRESS INCLUDING THE TENANT SPACE | | NUMBER SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET.6901 JOG ROAD OR 6901 OKEECHOBEE BLVD. ?? | | | | 2.RECTIFY THE MIXING OF JURISDICTIONS AS SHOWN IN THE | | TITLE BLOCK OF THE SUBMITTED PLAN SHEETS.THE AHJ AT | | THIS SCOPE OF WORK SITE IS THE CITY OF WEST PALM BEACH, | | NOT PALM BEACH COUNTY. | | | | 3.SPECIFY THE NEW WALL AND CEILING INTERIOR FINISH | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 4.AS PER LOCAL CODES, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM.AMEND OR ADD TO GENERAL | | ELECTRIC NOTE, SHEET E1. | | | | 5.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS IN THE | | SCOPE OF WORK SITE.ANY INSTALLATION AND/OR ALTERATION | | TO THE SPRINKLER SYSTEM REQUIRES SEPERATE PLANS AND | | PERM,IT. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INBCLUDE A | | RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN | | SHEET EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|