2008-03-27 14:41:21 | BUILDING PLAN REVIEW |
| PERMIT: 08030419 |
| ADD: 6901 OKEECHOBEE BLVD |
| CONT: RAPP CONSTRUCTION |
| TEL: (561)842-3299 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4)FIRE SPRINKLER PLANS LAYOUT REQUIRED TO SHOW THE |
| LOCATION OF THE SPRINKLER HEADS IN RELATIONS TO THE NEW |
| CONSTRUCTED WALLS. FBC 106.3.5.1.1(5) |
| |
| 5)THE ADDRESS ON THE APPLICATION 6901 OKEECHOBEE BLVD |
| DIFFERS FROM THE ADDRESS ON THE DRAWINGS WHICH SHOW |
| 6901 JOG ROAD E11. PLEASE COORDINATE THE ADDRESS ON THE |
| DRAWINGS WITH THE ADDRESS ON THE APPLICATION. THE SUITE |
| NUMBER SHALL ALSO CORRESPOND WITH THE EXISTING SUITES |
| OF THE BUILDING. |
| |
| 6)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE |
| SUBMITTED SHOWING THE EXISTING WALLS AND THE NEW WALLS. |
| SUBMIT A WALL LEGEND INDICATING EACH TYPE OF WALL AND |
| THE TYPE OF MATERIALS FOR EACH WALL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS. FBC 106.1.1. |
| |
| 7) 11-4.1.3(13) CONTROLS AND OPERATING MECHANISMS |
| IN ACCESSIBLE SPACES, ALONG ACCESSIBLE ROUTES, OR AS |
| PARTS OF ACCESSIBLE ELEMENTS (FOR EXAMPLE, LIGHT |
| SWITCHES AND DISPENSER CONTROLS ) SHALL COMPLY WITH |
| SECTION 11-4.27 . SHEET 8.1 ELEVATION #17. THE LOACTION |
| OF THE MICROWAVE SHALL MEET THE REQUIREMENTS OF |
| 11-4.27 |
| |
| 8)PROVIDE AN ELEVATION DETAIL DRAWING SHOWING WHERE A |
| PORTION OF THE RECEPTIONIST COUNTER HAS A MAXIMUM |
| HEIGHT OF 36 INCHES AND A MINIMUM LENGTH OF 36 INCHES |
| PER FBC 11-7 (2)(I). |
| |
| 9)SHEET 3.1 ROOM 105 (DIAGNOSTIC)435.5.1.3 PRIOR TO |
| CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT ARRANGEMENT |
| OF ALL NEW INSTALLATIONS, OR MODIFICATIONS OF EXISTING |
| INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND |
| ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE |
| SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND |
| APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER |
| REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE |
| FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| INTO CONSIDERATION. |
| |
| 10) FBC 435.5.1.3.1 |
| THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: |
| |
| 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S |
| RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; |
| GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY |
| WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S |
| BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. |
| |
| 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS |
| OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, |
| FLOOR AND CEILING OF THE ROOM CONCERNED. |
| |
| 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT |
| AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM |
| CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE |
| TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS |
| MAY BE PRESENT. |
| |
| 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT |
| AND THE MAXIMUM TECHNIQUE FACTORS. |
| |
| 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS |
| WHICH WILL BE PERFORMED WITH THE EQUIPMENT. PLEASE SEE |
| SECTION 435 FOR MORE INFORMATION. |
| |
| 11) FBC 1210.2 WALLS. |
| WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL |
| HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| PAINT ON DRYWALL IS NOT CONSIDERED A HARD SURFACE. |
| |
| 12)SHEET 10.1 THE ROOM FINISH SCHEDULE HAS SOME |
| ABBREVIATIONS W1/ W2 AND W3 WHAT TYPE OF FINISH DO THEY |
| REPRESENT? PLEASE GIVE THE MEANING LIKE THE OTHER |
| SYMBOLS HAVE. ADDITIONAL INFORMATION REQUIRED. WPB |
| AMENDMENTS 106.1.2 |
| |
| 13)FBC 712.3.1.2. ALL PENETRATIONS INTO ANY FIRE WALL |
| SHALL BE PROTECTED BY AN APPROVED PENETRATION FIRE STOP |
| SYSTEM INSTALLED AS TESTED IN ACCORDANCE WITH ASTM E |
| 814 OR UL 1479. PROVIDE THE UL NUMBER AND TESTED |
| ASSEMBLY FOR EACH PENETRATION INTO THE FIRE WALLS. |
| PLEASE SEE NEC 300.21 FOR MORE INFORMATION. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| FAX (561)805-6676 |
| [email protected] |