2008-03-18 14:52:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE RESUBMITTED MASTER BATH FLOOR PLANS AT A |
| MINIMUM SHALL BE DRAWN TO 1/8 INCH SCALE. PER (W.P.B.) |
| SECTION 106.1.3 QUALITY OF BUILDING PLANS. |
| |
| 2. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE |
| DELETED SHOWER BEING CAPPED OFF SHALL NOT HAVE ANY DEAD |
| ENDS AND THAT THE SHOWER BRANCH SHALL BE CAPPED OFF |
| WITHIN 2 FEET OF THE BUILDING DRAIN WASTE PIPE. PER FBC |
| PLUMBING SECTION 704.5 AND DEFINITIONS. |
| |
| 3. CLEARLY INDICATE THE SIZE OF THE PROPOSED SHOWER. |
| ALL SHOWER COMPARTMENTS SHALL HAVE A MINIMUM OF 900 |
| SQUARE INCHES. PER FBC PLUMBING SECTION 417.4. |
| |
| 4. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE |
| SHOWER WALLS AND FLOORS ARE COMPLIANT WITH THE |
| FOLLOWING FBC PLUMBING SECTIONS. |
| |
| 417.4.1 WALL AREA. |
| THE WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER |
| HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED |
| OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF |
| MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM) |
| ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT |
| THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT |
| WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR |
| SHOWER FLOOR. |
| |
| 417.5 SHOWER FLOORS OR RECEPTORS. |
| FLOOR SURFACES SHALL BE CONSTRUCTED OF IMPERVIOUS, |
| NONCORROSIVE, NONABSORBENT AND WATERPROOF MATERIALS. |
| |
| 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| **NOTE: THE SIGNATURE IS COPIED AND IS CUT OFF. PLEASE |
| COMPLY WITH AN ORIGINAL SIGNATURE. |
| |
| 6. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE |
| NEW CLOSET WILL BE BUILT BY OTHER'S. NOT IN THE SCOPE |
| OF THE PLUMBING PERMIT. PER (W.P.B.) SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |