2008-05-02 18:02:03 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| |
| 5. SHT D1.1 THE REMOVAL OF THE WOMEN'S TOILET ROOM IN |
| EFFECT DECREASES THE ACCESSIBILITY OF THE BUILDING. |
| SECTION 11-4.1.6(1)(A). THIS IS NOT ACCEPTABLE. PLEASE |
| CHOOSE AN ALTERNATIVE SUCH AS A UNISEX TOILET ROOM OR |
| ALTERING THE STALL IN THE EXISTING TOILET ROOM TO |
| COMPLY WITH THE ACCESSIBLITY CODE. |
| ****RESPONSE NOTED, BUT THE EXISTING STALL WITH THE LAV |
| INSTALLED STILL DECREASES THE ACCESSIBILITY AS THE LAV |
| NOW ENCROCHES INTO THE CLEAR FLOOR SPACE REQUIRED TO |
| TRANSFER FROM THE WHEECHAIR ONTO THE WATER CLOSET. |
| |
| 6. SHTS D1.1 & PE1.0 IN THE REMOVAL OF ANY PART OF A |
| DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION |
| 704.5. ALL DEMO'D/CAPPED LINES SHALL BE LEFT UNCOVERED |
| UNTIL FIELD INSPECTOR INSPECTION & APPROVAL. PLEASE |
| INDICATE ON PLANS. |
| ****RESPONSE NOTED, BUT THE NOTE IS NOT STATED ON THE |
| D1.1 SHEET. ALSO SHT D1.1 HAS NOT BEEN RESUBMITTED BUT |
| IS INDICATED ON THE INDEX OF DRAWINGS SHT CS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |