2008-05-02 18:02:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHT D1.1 THE REMOVAL OF THE WOMEN'S TOILET ROOM IN
 EFFECT DECREASES THE ACCESSIBILITY OF THE BUILDING.
 SECTION 11-4.1.6(1)(A). THIS IS NOT ACCEPTABLE. PLEASE
 CHOOSE AN ALTERNATIVE SUCH AS A UNISEX TOILET ROOM OR
 ALTERING THE STALL IN THE EXISTING TOILET ROOM TO
 COMPLY WITH THE ACCESSIBLITY CODE.
 ****RESPONSE NOTED, BUT THE EXISTING STALL WITH THE LAV
 INSTALLED STILL DECREASES THE ACCESSIBILITY AS THE LAV
 NOW ENCROCHES INTO THE CLEAR FLOOR SPACE REQUIRED TO
 TRANSFER FROM THE WHEECHAIR ONTO THE WATER CLOSET.
  
 6. SHTS D1.1 & PE1.0 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. ALL DEMO'D/CAPPED LINES SHALL BE LEFT UNCOVERED
 UNTIL FIELD INSPECTOR INSPECTION & APPROVAL. PLEASE
 INDICATE ON PLANS.
 ****RESPONSE NOTED, BUT THE NOTE IS NOT STATED ON THE
 D1.1 SHEET. ALSO SHT D1.1 HAS NOT BEEN RESUBMITTED BUT
 IS INDICATED ON THE INDEX OF DRAWINGS SHT CS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  