2008-05-10 15:23:45BUILDING PLAN REVIEW 2ND
 PERMIT: 08030318
 ADD: 4400 N. CONGRESS AVE.
 CONT: ROBB CONST. INC.
 TEL: (561)856-1643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:2ND5-10-08
 ACTION: DENIED
  
 1)OK
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
 NEW** SHEET D1.1 IS MISSING FROM BOTH SETS OF DRAWINGS.
 THE WOMEN?S BATHROOM DOES NOT MEET THE ACCESSIBILITY
 RREQUIREMENTS. FBC 11-4.1.6(A) NO ALTERATION SHALL
 DECREASE ANY ACCESSIBILITY OR USABILITY OF THE BUILDING
 SYSTEMS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726