2008-04-16 13:10:24 | *****DENIED***** |
| |
| |
| 01.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE - |
| SHALL BE REFERENCED. |
| |
| 02.ON THE SHEETS LS.1 AND LS.2, SHOW THE TRAVEL |
| DISTANCE TO THE EXITS NOT PASSING THROUGH |
| OBSTRUCTIONS. |
| |
| 03.FIRE EXTINGUISHER(S) ARE TO BE 2A10BC RATED. CLASS |
| C FIRE EXTINGUISHER NOTED ON SHEET LS.1 |
| |
| 04.ONLY ONE FIRE EXTINGUISHER NOTED ON SHEET LS.1, |
| DOES THIS SATISFY THE 75' TRAVEL DISTANCE. |
| |
| 05.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON THE |
| LIFE SAFETY SHEETS. |
| |
| 06.ON SHEET LS.2, IT APPEARS THAT THE DOUBLE DOORS OF |
| THE BOARD ROOM [227] SWING INTO AN EXIT ACCESS |
| CORRIDOR.BE ADVISED THAT DURING ITS SWING, ANY DOOR |
| IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF |
| OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, |
| PASSAGEWAY, ETC, WHEN FULLY OPEN. |
| |
| 07.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON E3.0 |
| AND E3.1 SHEETS.OPTIONAL IF SHOWN ON THE LIFE SAFETY |
| SHEETS. |
| |
| 08.CARD KEY ENTRY READERS NOTED ON SHEET E3.1, PLEASE |
| BE ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE |
| REQUIRED (ONCE THE MASTER PERMIT HAS BEEN ISSUED). |
| |
| 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| FIRE ALARM SYSTEM REMODEL AND/OR INSTALLATION (ONCE THE |
| MASTER PERMIT HAS BEEN ISSUED). |
| |
| 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS |
| PROJECT SITE. |
| |
| 11.PLAN SHEET A2.1 & A2.2 MISSING FROM ONE OF THE |
| SUBMITTED PLAN SETS. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| EACH ITEM WAS ADDRESSED |
| |
| |