Plan Review Notes
Plan Review Notes For Permit 08030318
Permit Number 08030318
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-04-16 13:10:24*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 02.ON THE SHEETS LS.1 AND LS.2, SHOW THE TRAVEL
 DISTANCE TO THE EXITS NOT PASSING THROUGH
 OBSTRUCTIONS.
  
 03.FIRE EXTINGUISHER(S) ARE TO BE 2A10BC RATED. CLASS
 C FIRE EXTINGUISHER NOTED ON SHEET LS.1
  
 04.ONLY ONE FIRE EXTINGUISHER NOTED ON SHEET LS.1,
 DOES THIS SATISFY THE 75' TRAVEL DISTANCE.
  
 05.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON THE
 LIFE SAFETY SHEETS.
  
 06.ON SHEET LS.2, IT APPEARS THAT THE DOUBLE DOORS OF
 THE BOARD ROOM [227] SWING INTO AN EXIT ACCESS
 CORRIDOR.BE ADVISED THAT DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF
 OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR,
 PASSAGEWAY, ETC, WHEN FULLY OPEN.
  
 07.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON E3.0
 AND E3.1 SHEETS.OPTIONAL IF SHOWN ON THE LIFE SAFETY
 SHEETS.
  
 08.CARD KEY ENTRY READERS NOTED ON SHEET E3.1, PLEASE
 BE ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED (ONCE THE MASTER PERMIT HAS BEEN ISSUED).
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM SYSTEM REMODEL AND/OR INSTALLATION (ONCE THE
 MASTER PERMIT HAS BEEN ISSUED).
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS
 PROJECT SITE.
  
 11.PLAN SHEET A2.1 & A2.2 MISSING FROM ONE OF THE
 SUBMITTED PLAN SETS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  