2008-03-19 09:00:47 | ** DENIED REVIEW ** |
| |
| |
| |
| |
| 1) NOTE: PLEASE SEE SETS OF SUBMITTED PLANS ARE NOT |
| COMPLETE AT THIS TIME. FOR EXAMPLE: PLEASE SEE COVER |
| SHEET WHICH LIST THE SHEET A2.1 AND A2.2 FOR REFLECTED |
| CEILING HOWEVER THESE ARE NOT IN SETS. PLEASE INCLUDE |
| SHOWING ALL THAT IS EXISTING MEETING. IS THERE ANY |
| CEILING WORK? |
| FBC 106.1.2, 106.3.1 FOR ADDITIONAL INFORMATION. |
| |
| 2) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS WHICH |
| ARE MISSING THE REQUIRED PRINTED NAME AND PRINTED |
| LICENSE NUMBER OF THE ARCHITECT OF RECORD. |
| FAC 61G1-16.004, FS 481 |
| |
| 3) NOTE: PLEASE SEE NOT ALL THE PANEL SCHEDULE |
| DESIGNATIONS ON THE RISER DIAGRAM CORRELATE WITH THE |
| DESIGNATIONS ON THE PANEL SCHEDULES. |
| PLEASE SEE FOR EXAMPLE: PANELS HP2C, HP2B ETC |
| PLEASE ALSO SEE THAT PANEL H2C ON E5.0 INDICATES THIS |
| PANEL AS A 25AMP MLO PANEL WHICH IS NOT POSSIBLE. THIS |
| PANEL CONTAINS A LOAD HIGHER THAN THE 25AMPS. |
| AS THIS PANEL DESIGNATION IS NOT ON RISER, CONFIRMATION |
| ON THIS CAN NOT BE DONE. |
| PLEASE COORDINATE ALL PANELS. |
| 240.4, 220, 230 ETC |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 4) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON |
| ELECTRICAL SHEET E5.0 FOR MDP ARE NOT FROM THE CURRENT |
| 2005 NEC. |
| PLEASE SEE 220.21 LISTED, HOWEVER THE 2005 NEC DOES NOT |
| CONTAIN A 220.21. |
| PLEASE ADJUST AS NEEDED. |
| FBC 106.1.2 |
| |
| ** PLEASE KNOW AS SOME PLANS WERE NOT SUBMITTED AND |
| SOME SCOPE OF WORK IS NOT CONFIRMED A COMPLETE REVIEW |
| COULD NOT BE DONE AT THIS TIME. THERE MAY VERY WELL BE |
| NEW COMMENTS ON THE FOLLOWING REVIEW. |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |