Plan Review Notes
Plan Review Notes For Permit 08030318
Permit Number 08030318
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-19 09:00:47** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE SETS OF SUBMITTED PLANS ARE NOT
 COMPLETE AT THIS TIME. FOR EXAMPLE: PLEASE SEE COVER
 SHEET WHICH LIST THE SHEET A2.1 AND A2.2 FOR REFLECTED
 CEILING HOWEVER THESE ARE NOT IN SETS. PLEASE INCLUDE
 SHOWING ALL THAT IS EXISTING MEETING. IS THERE ANY
 CEILING WORK?
 FBC 106.1.2, 106.3.1 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS WHICH
 ARE MISSING THE REQUIRED PRINTED NAME AND PRINTED
 LICENSE NUMBER OF THE ARCHITECT OF RECORD.
 FAC 61G1-16.004, FS 481
  
 3) NOTE: PLEASE SEE NOT ALL THE PANEL SCHEDULE
 DESIGNATIONS ON THE RISER DIAGRAM CORRELATE WITH THE
 DESIGNATIONS ON THE PANEL SCHEDULES.
 PLEASE SEE FOR EXAMPLE: PANELS HP2C, HP2B ETC
 PLEASE ALSO SEE THAT PANEL H2C ON E5.0 INDICATES THIS
 PANEL AS A 25AMP MLO PANEL WHICH IS NOT POSSIBLE. THIS
 PANEL CONTAINS A LOAD HIGHER THAN THE 25AMPS.
 AS THIS PANEL DESIGNATION IS NOT ON RISER, CONFIRMATION
 ON THIS CAN NOT BE DONE.
 PLEASE COORDINATE ALL PANELS.
 240.4, 220, 230 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON
 ELECTRICAL SHEET E5.0 FOR MDP ARE NOT FROM THE CURRENT
 2005 NEC.
 PLEASE SEE 220.21 LISTED, HOWEVER THE 2005 NEC DOES NOT
 CONTAIN A 220.21.
 PLEASE ADJUST AS NEEDED.
 FBC 106.1.2
  
 ** PLEASE KNOW AS SOME PLANS WERE NOT SUBMITTED AND
 SOME SCOPE OF WORK IS NOT CONFIRMED A COMPLETE REVIEW
 COULD NOT BE DONE AT THIS TIME. THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.