Plan Review Notes
Plan Review Notes For Permit 08030318
Permit Number 08030318
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-01 13:00:58BUILDING PLAN REVIEW
 PERMIT: 08030318
 ADD: 4400 N. CONGRESS AVE.
 CONT: ROBB CONST. INC.
 TEL: (561)856-1643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)PROVIDE FIRE SPRINKLER PLANS SHOWING THE
 SPRINKLER-HEAD LAYOUT AND THE EFFECTS OF THE NEW
 CONSTRUCTION IN RELATION OF THE EXISTING HEADS.
 FBC106.3.5.1.1 (5)*
  
 5)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 6)WPB AMENDMENTS 106.1.2*ADDITIONAL INFORMATION IS
 REQUIRED FOR THE CONSTRUCTABILITY OF WALL TYPE #2 WHICH
 IS NOT ATTACHED TO THE STRUCTURE OR CEILING ABOVE AND
 HAS AT LEAST SEVEN DOUBLE SOLID CORE DOORS INSTALLED IN
 THIS TYPE OF WALL. SEE SHEET A1.1 FOR MORE INFORMATION,
 ALSO ON SHEET A1.1 SOME OF THE WALLS ARE MAY BE LABELED
 WRONG.
  
 7)ARE THE EXISTING WALLS ATTACHED TO THE CEILING OR
 STRUCTURE ABOVE? IF THEY ARE ATTACHED TO EITHER
 STRUCTURE OR EXISTING CEILING WHY THE NEW INFILL WALLS
 WILL BE 4 INCHES BELOW THE CEILING?
  
 8)THE PLANS SHALL CLEARLY SHOW THE MEANS OF EGRESS
 WHICH SHALL INCLUDE EXIT ACCESS FBC 1013, EXIT FBC 1017
 AND EXIT DISCHARGE FBC 1023.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]