2008-03-13 11:41:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE 120,000 BTU GRIDDLE APPLIANCE SUBMITTAL NEEDS |
| VERIFICATION OF THE BTU LOAD (NOTE: THERE IS NO |
| INDICATION OF THE AMOUNT OF BURNERS) AND A LISTING FROM |
| A NATIONALLY RECOGNIZED TESTING LABORATORY. PER FBC |
| FUEL GAS SECTION 402.2 MAXIMUM GAS DEMAND AND NFPA 54. |
| |
| 2. THE 40,000 BTU STEAM TABLE APPLIANCE SUBMITTAL |
| NEEDS VERIFICATION OF THE BTU LOAD AND A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY. PER FBC FUEL |
| GASSECTION 402.2 MAXIMUM GAS DEMAND AND NFPA 54. |
| |
| 3. TWO COPIES OF THE MANUFACTURER'S SPECIFICATION |
| SHEETS FOR THE MP REGULATORS ARE REQUIRED CLEARLY |
| INDICATING THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, |
| AND A LISTING FROM A NATIONALLY RECOGIZED TESTING |
| LABORATORY. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, |
| SECTION 106.1 SUBMITTAL DOCUMENTS, FBC FUEL GAS SECTION |
| 402.2 MAXIMUM GAS DEMAND, AND NFPA 54. |
| |
| 4. CLEARLY SIZE ALL BRANCHES TO THE COOKLINE |
| APPLIANCES AND NOTE THE RED LINE CORRECTION TO THE |
| 122,000 BTU FRYERS (PLEASE REFERENCE THE ATTACHED FBC |
| FUEL GAS TABLE 402.4(2) ATTACHED TO THESE COMMENS |
| INDICATING THIS). PER TABLE 402.4(2) AND SECTION 401.1 |
| SCOPE. |
| |
| 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |