Plan Review Notes
Plan Review Notes For Permit 08030236
Permit Number 08030236
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-11 07:40:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE CODES USED TO DESIGN THE PROJECT. THE
 PLANS WILL BE REVIEWED PER THE FLORIDA BUILDING CODE
 2004 EDITION WITH AMENDMENTS UP TO AND INCLUDING THE
 2007 VERSION. SECTION 106.1.2 & FS 553.73(1)(A). PLEASE
 INDICATE ON PLANS.
  
 2. SHTA-1 PER TABLE 403.1 A SERVICE SINK AND A
 DRINKING FOUNTAIN ARE REQUIRED IN EACH TENANT SPACE.
 THE WATER COOLER SHOWN ON THE FLOOR PLAN DOES NOT MEET
 THE REQUIREMENT FOR A DRINKING FOUNTAIN. SECTION 410.1.
 PLEASE SHOW THE LOCATIONS OF THE SERVICE SINKS AND THE
 DRINKING FOUNTAINS ON THE FLOOR PLAN, SANITARY RISER
 DIAGRAM & THE WATER RISER DIAGRAM. SECTION 403.6.
  
 3. SHT A-3 BATHROOM ELEVATIONS. SHOW COMPLIANCE WITH
 THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS (BEHIND W/C)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 4. SHT A-3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. PLEASE SUBMIT A RISER DIAGRAM THAT WOULD
 REFLECT THE ACTUAL INSTALLATION. SECTION 106.3.5.1.3.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT REFLECT
 THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES ETC.
 SECTION 106.3.5.1.3(3)(13).
  
 6. PER SECTION 607.1 HOT WATER IS REQUIRED FOR BUILDING
 MAINTENANCE.
  
 7. SHT A-2 PER SECTION 1503.6 GUTTERS WITH DOWNSPOUTS
 ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES
 OR ON A ROOF ABOVE ANOTHER ROOF. PLEASE INDICATE GUTTER
 SIZE AND DOWNSPOUT SIZE AND WELL AS SQUARE FOOTAGE
 BEING DRAINED. DOWNSPOUTS SHALL DISCHARGE A MINIMUM 1
 FOOT FROM THE STRUCTRUE SIDEWALLS OF BUILDING.
  
 8. INFORMATIONAL: AN IRRIGATION PERMIT AND PLANS ARE
 REQUIRED. THIS CAN BE SUBMITTED BY THE IRRIGATION
 CONTRACTOR SEPARATELY AFTER BLDG PERMIT IS ISSUED.
 SECTION 106.3.5.1.3.
  
 9. SHTS L-1 & L-2 THE CERTIFICATE OF AUTHORIZATION,
 (FIRM LICENSE), IS REQUIRED IN THE TITLE BLOCK OF THE
 LANDSCAPE ARCHITECT PER FAC 61G1_16.004(2) & FS
 481.306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  