2008-03-18 16:28:37** DENIED REVIEW **
  
  
  
  
 1) NOTE: ** IMPORTANT**PLEASE SEE THERE ARE NUMEROUS
 ITEMS MISSING FOR MINIMUM CODE COMPLIANCE, A FULL AND
 COMPLETE REVIEW OF MANY ITEMS COULD NOT BE DONE. THERE
 MAY VERY WELL BE SEVERAL NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 FBC 106.3.1, 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR
 COMPLETE PLANS.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODE SHALL BE STATED
 ON PLANS RELEVANT TO THE MINIMUM DESIGNS. PLANS STATE
 THE LATEST EDITIONS WHICH IS NOT ACCEPTABLE. PLEASE BE
 SURE THE ELECTRICAL AS WELL AS COVER SHEET REFLECTS THE
 FOLLOWING REQUIRED FOR THIS TRADE REVIEWER.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 FBC 106.1.2, FS 553.73
  
 3) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 DIAGRAM SHOWING CODE COMPLIANCE. PLEASE SEE THE
 FOLLOWING SUB SECTIONS AS THERE ARE SEVERAL ITEMS
 MISSING.
 A) PLEASE SEE MISSING REQUIRED GROUNDING ELECTRODE
 SYSTEM. FOR EXAMPLE: PLEASE SEE ONE OF THE ITEMS
 MISSING IS THE REQUIRED FOOTER STEEL.
 B) PLEASE SEE MISSING DISCONNECTS FOR TENANTS.
 C) PLEASE SEE MISSING FEEDERS AFTER THE FIRST MEANS OF
 DISCONNECT.
 D) PLEASE SEE MISSING TAPPED CONDUCTORS.
 E) PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR(S)
 AFTER THE FIRST MEANS OF DISCONNECT.
 F) PLEASE SEE MISSING CONDUIT TO VERIFY CONDUIT FILL.
 G) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE
 EQUIPMENT.
 I) PLEASE SEE MAIN SHOWN AS NEMA 32, WHICH IS NOT
 CORRECT. THERE IS NO SUCH LISTING.
 J) PLEASE SEE MISSING FLOATING NEUTRAL REQUIRED AT
 METERS AFTER THE FIRST MEANS OF DISCONNECT.
 K) PLEASE SEE MISSING PANEL SCHEDULES.
 L) PLEASE SEE MISSING MINIMUM BRANCH CIRCUIT CONDUCTORS
 AND OVER CURRENT PROTECTION(S).
 ETC ETC.
 2005 NEC.
 215.5, 110.9, 90.7, 110.3, 250.122, 250.6, 250.66,
 250.50, 240.4, 310.16, 230.70, 240.24, 250.50, 408.4
 ETC
  
 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO
 NOT REFLECT ANY CALCULATIONS FROM THE NATIONAL
 ELECTRICAL CODE.
 PLEASE SEE NEC 220.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. PLEASE
 BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHTS.
 310.16, 240.4, 408.4
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE PLANS CALLS FOR 150AMP SERVICE
 TO EACH BAY HOWEVER BASED ON THE RISER DIAGRAM THIS ARE
 ONLY 100AMPS.
 PLEASE CORRELATE ALL.
 FBC106.1.2, NEC 215.5, 240.4, 220 ETC
  
 7) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC
 13-400.3.A, 13-400.3.B,ETC
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2
 FOR INTERIOR ALLOWANCES.
 PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ETC
 AS NO INFORMATION WAS SUBMITTED NO REVIEW OF ANY ITEMS
 COULD BE DONE.
 PLEASE SEE ALL OF CHAPTER 13 AND COMMENTS FROM OTHER
 TRADES.\
  
 8) NOTE: PLEASE SUBMIT PLANS WHICH ARE SIGNED, DATED
 AND SEALED BY THE DESIGN PROFESSIONAL. PLEASE SEE ONE
 SET SUBMIT HAD THE DESIGNER OF RECORD SIGNATURE
 SCRATCHED OUT AND MISSING RAISED SEAL.
 PLEASE SEE FAC 61G15-23.002 AND FS471.025 AS EACH
 SECTION NOTED REQUIRES BOTH SETS TO BE SIGNED, DATED
 AND SEALED BY THE DESIGNER OF RECORD.
  
 9) NOTE: PLEASE SEE THE LANDSCAPE ARCHITECTURAL
 PLANS/TITLE BLOCKS ARE MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219.
 PLEASE ALSO SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF
 SAID DESIGNER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 ** DUE TO THE EXTENT OF COMMENTS ABOVE, ONE COPY OF
 PLANS IS BEING RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.