2008-03-18 16:28:37 | ** DENIED REVIEW ** |
| |
| |
| |
| |
| 1) NOTE: ** IMPORTANT**PLEASE SEE THERE ARE NUMEROUS |
| ITEMS MISSING FOR MINIMUM CODE COMPLIANCE, A FULL AND |
| COMPLETE REVIEW OF MANY ITEMS COULD NOT BE DONE. THERE |
| MAY VERY WELL BE SEVERAL NEW COMMENTS ON THE FOLLOWING |
| REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| FBC 106.3.1, 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR |
| COMPLETE PLANS. |
| |
| 2) NOTE: PLEASE SEE THE FOLLOWING CODE SHALL BE STATED |
| ON PLANS RELEVANT TO THE MINIMUM DESIGNS. PLANS STATE |
| THE LATEST EDITIONS WHICH IS NOT ACCEPTABLE. PLEASE BE |
| SURE THE ELECTRICAL AS WELL AS COVER SHEET REFLECTS THE |
| FOLLOWING REQUIRED FOR THIS TRADE REVIEWER. |
| FBC 2004 W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| FBC 106.1.2, FS 553.73 |
| |
| 3) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER |
| DIAGRAM SHOWING CODE COMPLIANCE. PLEASE SEE THE |
| FOLLOWING SUB SECTIONS AS THERE ARE SEVERAL ITEMS |
| MISSING. |
| A) PLEASE SEE MISSING REQUIRED GROUNDING ELECTRODE |
| SYSTEM. FOR EXAMPLE: PLEASE SEE ONE OF THE ITEMS |
| MISSING IS THE REQUIRED FOOTER STEEL. |
| B) PLEASE SEE MISSING DISCONNECTS FOR TENANTS. |
| C) PLEASE SEE MISSING FEEDERS AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| D) PLEASE SEE MISSING TAPPED CONDUCTORS. |
| E) PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR(S) |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| F) PLEASE SEE MISSING CONDUIT TO VERIFY CONDUIT FILL. |
| G) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE |
| EQUIPMENT. |
| I) PLEASE SEE MAIN SHOWN AS NEMA 32, WHICH IS NOT |
| CORRECT. THERE IS NO SUCH LISTING. |
| J) PLEASE SEE MISSING FLOATING NEUTRAL REQUIRED AT |
| METERS AFTER THE FIRST MEANS OF DISCONNECT. |
| K) PLEASE SEE MISSING PANEL SCHEDULES. |
| L) PLEASE SEE MISSING MINIMUM BRANCH CIRCUIT CONDUCTORS |
| AND OVER CURRENT PROTECTION(S). |
| ETC ETC. |
| 2005 NEC. |
| 215.5, 110.9, 90.7, 110.3, 250.122, 250.6, 250.66, |
| 250.50, 240.4, 310.16, 230.70, 240.24, 250.50, 408.4 |
| ETC |
| |
| 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO |
| NOT REFLECT ANY CALCULATIONS FROM THE NATIONAL |
| ELECTRICAL CODE. |
| PLEASE SEE NEC 220. |
| FBC 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. PLEASE |
| BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND |
| EXIT LIGHTS. |
| 310.16, 240.4, 408.4 |
| FBC 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE THE PLANS CALLS FOR 150AMP SERVICE |
| TO EACH BAY HOWEVER BASED ON THE RISER DIAGRAM THIS ARE |
| ONLY 100AMPS. |
| PLEASE CORRELATE ALL. |
| FBC106.1.2, NEC 215.5, 240.4, 220 ETC |
| |
| 7) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC |
| 13-400.3.A, 13-400.3.B,ETC |
| PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2 |
| FOR INTERIOR ALLOWANCES. |
| PLEASE SEE MISSING LIGHTING CONTROLS PER |
| 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ETC |
| AS NO INFORMATION WAS SUBMITTED NO REVIEW OF ANY ITEMS |
| COULD BE DONE. |
| PLEASE SEE ALL OF CHAPTER 13 AND COMMENTS FROM OTHER |
| TRADES.\ |
| |
| 8) NOTE: PLEASE SUBMIT PLANS WHICH ARE SIGNED, DATED |
| AND SEALED BY THE DESIGN PROFESSIONAL. PLEASE SEE ONE |
| SET SUBMIT HAD THE DESIGNER OF RECORD SIGNATURE |
| SCRATCHED OUT AND MISSING RAISED SEAL. |
| PLEASE SEE FAC 61G15-23.002 AND FS471.025 AS EACH |
| SECTION NOTED REQUIRES BOTH SETS TO BE SIGNED, DATED |
| AND SEALED BY THE DESIGNER OF RECORD. |
| |
| 9) NOTE: PLEASE SEE THE LANDSCAPE ARCHITECTURAL |
| PLANS/TITLE BLOCKS ARE MISSING THEIR CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED PER FAC 61G1-16.004 |
| AND FS 481.219. |
| PLEASE ALSO SEE THE TITLE BLOCKS ARE MISSING THE |
| REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF |
| SAID DESIGNER. |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES. |
| |
| ** DUE TO THE EXTENT OF COMMENTS ABOVE, ONE COPY OF |
| PLANS IS BEING RETAINED BY THIS OFFICE. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |