Plan Review Notes
Plan Review Notes For Permit 08030151
Permit Number 08030151
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-13 14:31:032004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WIIL BE REQUIRED.
  
 2) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 FBC EXISTING BUILDING CHAPTER 3.
  
 3) ON SHEET A1 THE TYPE OF CONSTRUCTION IS INCORRECTLY
 LISTED AS TYPE 2. IT IS ACTUALLY TYPE V. PLEASE
 CORRECT. SEE FBC SECTION 602.
  
 4) ITEM #6 UNDER THE SCOPE OF WORK ON SHEET A1
 INDICATES THAT THE EXISTING STRUCTURE IS TO BE MADE TO
 COMPLY WITH THE 2004 FBC. IF THIS IS ACCURATE PROVIDE A
 LIST SPECIFYING THE ITEMS THAT WILL BE DONE TO BRING
 THE ENTIRE STRUCTURE INTO COMPLIANCE WITH THE 2004 FBC
 AND INCREASE THE VALUE OF THE WORK ON THE APPLICATION.
 THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION DOES
 NOT STATE THAT THE ENTIRE STRUCTURE IS TO BE UPGRADED
 TO COMPLY WITH THE 2004 FBC. NO STRUCTURAL WORK IS
 LISTED. PLEASE CORRECT.
  
 5) ITEM #2 UNDER THE SCOPE OF WORK ON SHEET A1
 INDICATES THAT EXISTING WINDOWS ARE TO BE FIXED OR
 REPAIRED. THE PERMIT APPLICATION INDICATES THAT WINDOWS
 AND DOORS ARE TO BE REPLACED. PLEASE CLARIFY.
  
 6)THE TYPICAL EXTERIOR WALL SECTION ON A2 IS SPCIFIED
 AS NON-BEARING, BUT A BEARING WALL IS SHOWN. PLEASE
 CORRECT.
  
 7) THE ROOF NOTE ON THE TYPICAL EXTERIOR WALL SECTION
 ON A2 INDICATES THAT NEW SHINGLES ARE TO BE INSTALLED
 TO MATCH THE EXISTING. PLEASE CORRECT.
  
 8) IF NO STRUCTURAL WORK IS BEING DONE, WHY ARE THE
 WALL SECTIONS AND WINDOW FRAMING DETAILS ON THE PLANS.
 PLEASE CLARIFY.
  
 9) THE WALL LEDGEND AND WALL SCHEDULE ON A1 HAVE
 CONFLICTING INFORMATION. PLEASE CORRECT.
  
 10) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SPECIFY THE MOUNT TYPE, FASTENER TYPE AND
 SPACING, PANEL SPAN, EDGE DISTANCE, ETC. SEE ATTACHED
 SAMPLE.
  
 11) BATHROOM WINDOW TO HAVE SAFETY GLAZING IN
 COMPLIANCE WITH R308.3.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE INSWING EXTERIOR
 DOOR. DCA RULE 9B-72
  
 13) PRODUCT APPROVALS WERE SUBMITTED CASEMENT WINDOWS,
 HOWEVER THERE ARE NOT ANY SHOWN ON THE PLANS. PLEASE
 INDICATE THE CASEMENT WINDOWS ON THE PLANS OR REMOVE
 THE PRODUCT APPROVALS FOR THEM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW