2008-04-09 18:46:06 | BUILDING PLAN REVIEW #2 |
| PERMIT: 08030142 |
| ADD: 230 MIRAMAR WAY |
| CONT: SCHMIDT ELECTRIC, INC. |
| TEL: (561)588-6881 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 2ND 4-9-08 |
| ACTION: DENIED |
| |
| 1)OK |
| |
| *NO RESPONSE NOT ADDRESSED* |
| 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| *NO RESPONSE NOT ADDRESSED* |
| 3)1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR. |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5.COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF TO BE USED FOR THE SELECTION OF |
| EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| **THE TRACED SIGNATURE OVER THE PHOTO-COPY SIGNATURE IS |
| NOT ACCEPTABLE. OUR OFFICE WILL RETAIN ONE REPORT AS |
| EVIDENCE** |
| 4)61G15-23.002A PROFESSIONAL ENGINEER SHALL SIGN |
| HIS NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS PROVIDED |
| TO THE OWNER OR THE OWNER?S REPRESENTATIVE, OR OTHER |
| DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT AND |
| BEING FILED FOR PUBLIC RECORD. THE SHEET WITH P.E. |
| #22920 NEEDS TO BE SIGN DATED AND SEALED BY THE |
| INDIVIDUAL. |
| |
| **THE TRACED SIGNATURE OVER THE PHOTO-COPY SIGNATURE IS |
| NOT ACCEPTABLE.** |
| 5)THE LETTER FROM STRUCTURAL ENGINEER SONIA TORRES |
| REQUIRES AN ORIGINAL SIGNATURE, PHOTOCOPY SIGNATURES |
| ARE NOT ACCEPTABLE. ALL INFORMATION BEING FILED FOR |
| PUBLIC RECORD SHALL CONTAIN THE ORIGINAL SIGNATURE OF |
| THE RESPONSIBLE PERSON. |
| |
| 61G15-23.002EACH SHEET OF PLANS AND PRINTS WHICH MUST |
| BE SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., |
| SHALL BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL |
| ENGINEER IN RESPONSIBLE CHARGE |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |