Date Text
2008-03-11 10:39:30 
  
  
 PROVISO
  
 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE
 BUILDING OR STRUCTURE.
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED.
  
 ALL GENERATOR CONDUCTORS MUST BE CAPABLE OF BEING
 DISCONNECTED ELECTRICALLY ON THE OUTSIDE OF THE
 BUILDING WITHOUT GOING TO THE ROOF TO DISCONNECT THE
 BREAKER AT THAT POINT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  