Plan Review Notes For Permit 08030142 |
Permit Number |
08030142 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-11 10:39:30 | | | | | | | PROVISO | | | | 225.31 DISCONNECTING MEANS | | MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL | | UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE | | BUILDING OR STRUCTURE. | | 225.32 LOCATION | | THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER | | INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED | | OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR | | STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A | | READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS | | SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED. | | | | ALL GENERATOR CONDUCTORS MUST BE CAPABLE OF BEING | | DISCONNECTED ELECTRICALLY ON THE OUTSIDE OF THE | | BUILDING WITHOUT GOING TO THE ROOF TO DISCONNECT THE | | BREAKER AT THAT POINT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|