Plan Review Notes
Plan Review Notes For Permit 08030139
Permit Number 08030139
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-13 13:36:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} 210.70(A) (2) (B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT. SHOW
 COMPLIANCE AT THE NEW DOOR LOCATION.
  
 2} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718