Plan Review Notes
Plan Review Notes For Permit 08030139
Permit Number 08030139
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-12 07:40:282004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE PLANS WITH THE ENGINEER'S TITLE BLOCK IS
 REQUIRED TO BE SIGNED SEALED AND DATED BY THE ENGINEER.
 FS 471 AND FBC 106.1* CITY AMENDMENTS
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE NEW DOOR OPENING
 AT THE EXISTING WINDOW. PROVIDE BUCK DETAILS.FBC
 106.1.1* CITY AMENDMENTS
  
 4) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 NEW DOOR AND NEW WINDOWS THAT WERE MISSED. FBC TABLE R
 301.2(2)
  
 5) SPECIFY WHICH WINDOWS ARE SINGLE HUNG AND CASEMENT.
 FBC 106.1.1* CITY AMENDMENTS
  
 6) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS AS REQUIRED BY RULE 9B-72 F.A.C.
  
 7) SUBMIT TWO (2) COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE CONNECTION
 TYPE, FASTENER TYPE AND SPACING, EDGE DISTANCE, SPANS,
 ETC. SEE SAMPLE SCHEDULE ATTACHED.
  
 8) SHOW COMPLIANCE WITH R311.6.3 HANDRAILS REQUIRED.
 HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF ALL
 RAMPS EXCEEDING A SLOPE OF ONE UNIT VERTICAL IN 12
 UNITS HORIZONTAL (8.33-PERCENT SLOPE).
  
 9) SHOW COMPLIANCE WITH R 311.6.3.2 HANDRAIL GRIP SIZE
 AND R311.6.3.3 CONTINUITY.
  
 10) AN EXTERIOR LIGHT FIXTURE WITH A SWITCH IS REQUIRED
 AT THE NEW EXTERIOR DOOR PER THE 2005 NEC SECTION
 210.70(2)(B).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]