Plan Review Notes
Plan Review Notes For Permit 08030079
Permit Number 08030079
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-10 15:53:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.PLEASE
 NOTE THAT THERE IS AN ERROR IN THIS NOA.PLEASE SEE
 NOA 07-0822.10.
  
 ENGINEERING IS REQUIRED FOR THE ASSEMBLY SELECTED AS
 THE DESIGN PRESSURE FOR THIS ASSEMBLY IS -60PSF (-89
 MINIMUM REQUIRED FOR ZONE 3).HOWEVER, SEE THE
 ASSEMBLY ON PAGE 22.THIS IS A SIMILAR ASSEMBLY WHICH
 DOES NOT REQUIRE ENGINEERING AS THE SYSTEM LIMITATION
 IS -112.5.EITHER SELECT A DIFFERENT ASSEMBLY OR
 PROVIDE ENGINEERING FOR ENHANCED FASTENING FOR ZONES 2
 AND 3.