2008-03-06 14:30:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)FOR THE FLAT ROOF, INDICATE WHICH FASTENER YOU ARE
 USING (APPROVED ASSEMBLY PAGE) AS THE OPTIONS HAVE
 DIFFERENT PRESSURE LIMITATIONS.
  
 2.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.THE LETTER STATES THAT
 ATTACHMENT WILL BE EVERY 4" OC, BUT DOES NOT STATE
 NUMBER OF ROWS.PLEASE REVISE TO INCLUDE NUMBER OF
 ROWS, AND SPECIFY WHETHER THIS NUMBER INCLUDES THE LAP
 ROW.THE ASSEMBLY SELECTED HAS OPTIONS RANGING FROM
 TWO FIELD ROWS TO FOUR FIELD ROWS.WITHOUT COMPLETE
 ENHANCED FASTENING AND FASTENER INFORMATION, CODE
 COMPLIANCE CANNOT BE DETERMINED.
  
  
  