2008-12-24 14:11:22** DENIED REVIEW OF REVISIONS**
  
  
 1) NOTE: METHOD *C* FLA-COMM SUBMITTED DOES NOT CONTAIN
 ANY INPUT DATA REPORT. THE DESIGN WATTAGE IS HIGHER
 THAN ALLOWANCE PER FBC 13-415.2.ABC.1.1,.1.2, TABLE
 13-415.2.C.
 PLEASE SEE PLANS WHICH CONTAINS METHOD *B* TABLE
 13-415.2.B FOR COMPLIANCE WHICH HAS NOT BEEN UPDATED
 FOR CHANGES IN LIGHTING ON PLANS.
 PLEASE SEE 13-415.2.ABC.1. IT IS NOT PERMISSIBLE BY
 CODE TO USE MULTIPLE METHODS OF ENERGY CALCULATIONS TO
 TRY AND ACHIEVE CODE COMPLIANCE.
  
 ** PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR
 BEAUTY CASES IN WHICH EXEMPTION IN 13-415.2.ABC.1 IS
 BEING APPLIED.
 110.3, 90.7.
 FBC 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SUBMIT COMPLETE UPDATE AND REVISED
 PLANS FOR CODE COMPLIANCE. THE INPUT DATA REPORT AS
 STATED ON SHEET TWO OF THE SUBMITTED CALCULATIONS MUST
 ACCOMPANY THE SUBMITTED DOCUMENTS. NO REVIEW FOR CODE
 COMPLIANCE CAN BE ACHIEVED.
 FBC 106.1.1 FOR COMPLETE INFORMATION, CLARITY AND
 COORDINATION.
 CODE SECTIONS NOTED IN NOTE #1.
  
 3) NOTE: FEE DUE FOR ENERGY CALCULATIONS SUBMITTED AS A
 SUBMITTAL. THIS IS ACTUALLY A REVISION TO BE REVIEWED
 AND COORDINATED WITH PLANS SUBMITTED.
  
 4) NOTE: LETTERS SUBMITTED BY CITY PLACE AND RCC WERE
 NOT CORRECTLY NOTARIZED PER FS 117.05. PLACING THE
 NOTARY STAMP ON LETTER AND SIGNING IS NOT THE ONLY
 INFORMATION REQUIRED. LETTER FROM RCC DOES CONTAIN SOME
 MORE INFORMATION HOWEVER NOT ALL. A COMPLETED STATEMENT
 IN SECTION GIVEN CAN BE VIEWED ON LINE AT STATE
 WEBSITE. THE INFORMATION CAN BE FOUND IN SECTION
 117.05(12)(B).
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  