2008-06-26 17:03:35 | ** DENIED3RD AUDIT ** |
| |
| |
| 1) NOTE:PLEASE SEE THE SUBMITTED FLA-COM ENERGY |
| CALCULATIONS STATES METHOD *C* HOWEVER PLEASE SEE |
| 13-415.2.C, 13-415.2.C.1. THE SUBMITTED CALCULATIONS |
| ARE NOT CODE COMPLIANT BASED ON *C* AS METHOD C FOR |
| AREA ONLY ALLOWS 1.5 WATTS/PER/SQFT. |
| BASED ON THE SQUARE FOOTAGE THIS WOULD BE SUBSTANTIALLY |
| LOWER THAN THE DESIGN WATTAGE OF JUST OVER |
| 18,000WATTS. |
| THE OTHER ITEM IS THE SHEET ON PLANS SHOWS SPACE BY |
| SPACE FOR METHOD *B*.PLEASE SEE THE SALES AREA AS A |
| TOTAL IS SHOWING 2.1 WATTS/PER/SQFT ALLOWANCE WHICH |
| EXCEEDS THE MAXIMUM ALLOWANCES ON TABLE 13-415.2.B. |
| PLEASE LOOK AT SALES AREAS ON THE TABLE WHICH HAS A |
| BASE ALLOWANCE OF 1.7, NOT 2.1. |
| WHICH IS GOING TO BE USED? |
| PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3. |
| |
| BASED ON ALL CODE SECTIONS GIVEN ABOVE AND BASED ON THE |
| FACT THE LIGHTING DESIGN IS SUBSTANTIALLY OVER THE |
| MAXIMUM ALLOWANCES ALLOWED BY THE CODE. |
| THIS AUDIT SHALL BE PLACED INTO A FAILED STATUS FOR THE |
| THIRD TIME. |
| |
| 2) NOTE: PLEASE SEE AREAS AROUND DRESSING ROOMS. WHERE |
| IS THE LIGHTING CONTROL? THIS IS ONE EXAMPLE. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR ALL |
| REQUIRED CONTROLS ONCE AGAIN. |
| |
| 3) NOTE: PLEASE SEE ONE SET OF THE SUBMITTED FLA COM |
| CALCULATIONS WERE INDEED PHOTO-COPIES AND NOTE |
| ORIGINAL. |
| FAC 61G15-23.002, FS 471.025 |
| |
| ** PLEASE KNOW ELECTRICAL LIGHTING SHEETS, ELECTRICAL |
| SHEETS WITH LIGHTING CALCULATIONS AS WELL AS FLACOM |
| CALCULATIONS HAVE BEEN RETAINED BY THIS OFFICE. |
| |
| ** A CALL WAS PLACED TO THE ENGINEERED SIGNED AND |
| SEALED ON PLANS AS OF THIS REVIEW. MR. VAN STRATEN WAS |
| IN NEED OF LOCATING THE ELECTRICAL DESIGNER WHO WORKED |
| ON PROJECT.HE WAS NOT ABLE TO GO OVER COMMENTS. |
| |
| |
| |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |