Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-26 17:03:35** DENIED3RD AUDIT **
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED FLA-COM ENERGY
 CALCULATIONS STATES METHOD *C* HOWEVER PLEASE SEE
 13-415.2.C, 13-415.2.C.1. THE SUBMITTED CALCULATIONS
 ARE NOT CODE COMPLIANT BASED ON *C* AS METHOD C FOR
 AREA ONLY ALLOWS 1.5 WATTS/PER/SQFT.
 BASED ON THE SQUARE FOOTAGE THIS WOULD BE SUBSTANTIALLY
 LOWER THAN THE DESIGN WATTAGE OF JUST OVER
 18,000WATTS.
 THE OTHER ITEM IS THE SHEET ON PLANS SHOWS SPACE BY
 SPACE FOR METHOD *B*.PLEASE SEE THE SALES AREA AS A
 TOTAL IS SHOWING 2.1 WATTS/PER/SQFT ALLOWANCE WHICH
 EXCEEDS THE MAXIMUM ALLOWANCES ON TABLE 13-415.2.B.
 PLEASE LOOK AT SALES AREAS ON THE TABLE WHICH HAS A
 BASE ALLOWANCE OF 1.7, NOT 2.1.
 WHICH IS GOING TO BE USED?
 PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3.
  
 BASED ON ALL CODE SECTIONS GIVEN ABOVE AND BASED ON THE
 FACT THE LIGHTING DESIGN IS SUBSTANTIALLY OVER THE
 MAXIMUM ALLOWANCES ALLOWED BY THE CODE.
 THIS AUDIT SHALL BE PLACED INTO A FAILED STATUS FOR THE
 THIRD TIME.
  
 2) NOTE: PLEASE SEE AREAS AROUND DRESSING ROOMS. WHERE
 IS THE LIGHTING CONTROL? THIS IS ONE EXAMPLE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR ALL
 REQUIRED CONTROLS ONCE AGAIN.
  
 3) NOTE: PLEASE SEE ONE SET OF THE SUBMITTED FLA COM
 CALCULATIONS WERE INDEED PHOTO-COPIES AND NOTE
 ORIGINAL.
 FAC 61G15-23.002, FS 471.025
  
 ** PLEASE KNOW ELECTRICAL LIGHTING SHEETS, ELECTRICAL
 SHEETS WITH LIGHTING CALCULATIONS AS WELL AS FLACOM
 CALCULATIONS HAVE BEEN RETAINED BY THIS OFFICE.
  
 ** A CALL WAS PLACED TO THE ENGINEERED SIGNED AND
 SEALED ON PLANS AS OF THIS REVIEW. MR. VAN STRATEN WAS
 IN NEED OF LOCATING THE ELECTRICAL DESIGNER WHO WORKED
 ON PROJECT.HE WAS NOT ABLE TO GO OVER COMMENTS.
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  