Date |
Text |
2008-05-05 10:14:07 | ** DENIEDAUDIT ** |
| |
| 1) NOTE: PLEASE SEE THE NOTICE TO BUILDING OFFICIAL |
| NEEDS TO COORDINATE WITH THE SIGNED AFFIDAVITS. PLEASE |
| SEE THESE SHOW SEPARATE PRIVATE PROVIDERS AS THE |
| RESPONSIBLE ENGINEERS. |
| PLEASE SUBMIT. |
| FS 553.791 |
| |
| 2) NOTE: PLEASE SEE THE AFFIDAVITS DO NOT LIST THE |
| ENERGY/PERFORMANCE CALCULATIONS. |
| FS553.791 |
| |
| 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE CALCULATIONS |
| DATED 2/4/08 WERE SUBMITTED. |
| PLEASE SEE THE SUBMITTED INPUT DATA REPORT WHICH |
| FOLLOWS DOES NOT CORRELATE WITH LIGHTING ON PLANS. IN |
| FACT THERE ARE SEVERAL LIGHT FIXTURES ON PLANS WHICH |
| ARE NOT ON THE IDR. |
| PLEASE SEE FOR EXAMPLE: PLANS CLEARLY SHOW EXTERIOR |
| LIGHTS, HOWEVER THE IDR DO NOT INDICATE ANY LIGHTS. |
| THIS IS ACTUALLY BLANK. |
| PLEASE SEE 13-415.2.ABC.1.3. |
| PLEASE SEE FOR EXAMPLE: |
| TRACK LIGHTS ARE NOT SHOWN PER 13-415.2.ABC.1.1, .1.2. |
| |
| ** THESE ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED |
| LIST OF ALL ITEMS WHICH DO NOT CORRELATE WITH PLANS. |
| |
| 4) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW. THERE |
| IS NOT ENOUGH INFORMATION FOR REVIEW OF THE REQUIRED |
| LIGHTING CONTROL SYSTEM. THE RESPONSE LETTER STATES |
| THREE OVER RIDES WERE ADDED HOWEVER WHERE ARE THE |
| LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2, |
| .1.3 AND .1.4? |
| THERE ARE A COUPLE OF NOTES ON PLANS WHICH MENTIONS |
| THERE WILL BE SOME SORT OF LIGHTING CONTROLS HOWEVER |
| PLACING NOTES ON PLANS IN LIEU OF SHOWING CODE |
| COMPLIANCE IS NOT PERMITTED. |
| THE RESPONSE LETTER ALSO STATES IT IS *NOT CAPABLE* TO |
| SHOW ZONES. THIS OFFICE DOES NOT UNDERSTAND HOW MEETING |
| * MINIMUM REQUIRED* BY CODE IS NOT POSSIBLE. |
| ONE AGAIN PLEASE SHOW COMPLETE LIGHTING CONTROL(S) |
| SYSTEM(S) PER SECTIONS GIVEN ABOVE. |
| |
| 5) NOTE: PLEASE SEE SECTION NOTED ABOVE FOR EXTERIOR |
| LIGHTS PER 13-415.1.ABC.1.4. |
| PLEASE COMPLETE WITH ONE OF THE TWO MINIMUM REQUIRED BY |
| CODE. |
| |
| 6) NOTE: PLEASE SEE COMMENT #9 FROM PREVIOUS REVIEW. |
| PLEASE SEE ONCE AGAIN THESE ARE *STANDARD SWITCHES* |
| BEING NOTED IN THE SPECIFICATIONS. |
| SEE NOTE #4 ABOVE. |
| |
| 7) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS |
| GIVEN. |
| FS 553.80(2)(B) IS APPLICABLE TO ANY PROJECT AS IT IS |
| FOR THE DESIGN PROFESSIONAL WITH RESPECT TO REPEAT |
| COMMENTS FOR CODE COMPLIANCE. |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |