Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-05 10:14:07** DENIEDAUDIT **
  
 1) NOTE: PLEASE SEE THE NOTICE TO BUILDING OFFICIAL
 NEEDS TO COORDINATE WITH THE SIGNED AFFIDAVITS. PLEASE
 SEE THESE SHOW SEPARATE PRIVATE PROVIDERS AS THE
 RESPONSIBLE ENGINEERS.
 PLEASE SUBMIT.
 FS 553.791
  
 2) NOTE: PLEASE SEE THE AFFIDAVITS DO NOT LIST THE
 ENERGY/PERFORMANCE CALCULATIONS.
 FS553.791
  
 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE CALCULATIONS
 DATED 2/4/08 WERE SUBMITTED.
 PLEASE SEE THE SUBMITTED INPUT DATA REPORT WHICH
 FOLLOWS DOES NOT CORRELATE WITH LIGHTING ON PLANS. IN
 FACT THERE ARE SEVERAL LIGHT FIXTURES ON PLANS WHICH
 ARE NOT ON THE IDR.
 PLEASE SEE FOR EXAMPLE: PLANS CLEARLY SHOW EXTERIOR
 LIGHTS, HOWEVER THE IDR DO NOT INDICATE ANY LIGHTS.
 THIS IS ACTUALLY BLANK.
 PLEASE SEE 13-415.2.ABC.1.3.
 PLEASE SEE FOR EXAMPLE:
 TRACK LIGHTS ARE NOT SHOWN PER 13-415.2.ABC.1.1, .1.2.
  
 ** THESE ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED
 LIST OF ALL ITEMS WHICH DO NOT CORRELATE WITH PLANS.
  
 4) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW. THERE
 IS NOT ENOUGH INFORMATION FOR REVIEW OF THE REQUIRED
 LIGHTING CONTROL SYSTEM. THE RESPONSE LETTER STATES
 THREE OVER RIDES WERE ADDED HOWEVER WHERE ARE THE
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 .1.3 AND .1.4?
 THERE ARE A COUPLE OF NOTES ON PLANS WHICH MENTIONS
 THERE WILL BE SOME SORT OF LIGHTING CONTROLS HOWEVER
 PLACING NOTES ON PLANS IN LIEU OF SHOWING CODE
 COMPLIANCE IS NOT PERMITTED.
 THE RESPONSE LETTER ALSO STATES IT IS *NOT CAPABLE* TO
 SHOW ZONES. THIS OFFICE DOES NOT UNDERSTAND HOW MEETING
 * MINIMUM REQUIRED* BY CODE IS NOT POSSIBLE.
 ONE AGAIN PLEASE SHOW COMPLETE LIGHTING CONTROL(S)
 SYSTEM(S) PER SECTIONS GIVEN ABOVE.
  
 5) NOTE: PLEASE SEE SECTION NOTED ABOVE FOR EXTERIOR
 LIGHTS PER 13-415.1.ABC.1.4.
 PLEASE COMPLETE WITH ONE OF THE TWO MINIMUM REQUIRED BY
 CODE.
  
 6) NOTE: PLEASE SEE COMMENT #9 FROM PREVIOUS REVIEW.
 PLEASE SEE ONCE AGAIN THESE ARE *STANDARD SWITCHES*
 BEING NOTED IN THE SPECIFICATIONS.
 SEE NOTE #4 ABOVE.
  
 7) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS
 GIVEN.
 FS 553.80(2)(B) IS APPLICABLE TO ANY PROJECT AS IT IS
 FOR THE DESIGN PROFESSIONAL WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]