Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-08 13:31:32AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE PLANS IS REQUIRED. THE SIGNATURE OF
 THE PERSON SEALING THE DOCUMENTS IS REQUIRED. FAC
 61G1-16.003, 61G1-16.004(5)(6) & FS 481.2055. IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH INITALS.
 IF IT IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT
 THEN A SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR
 OUR FILES.
  
 2. SHT A01.1 DEMO KEY NOTE #10 INDICATES CAPPING
 PLUMBING IN THE NEAREST DEMISING WALL. SECTION 704.5
 PROHIBITS DEAD ENDS. PLEASE SHOW COMPLIANCE WITH
 SECTION AND SHOW THE LOCATION OF ALL DEMO'D PIPING.
  
 3. SHT A13.1 DETAIL D ELEVATION D-4 SHOWS THE DISPENSER
 MINIMUM OF 15" ABOVE THE FLOOR. PER SECTION 11-4.16.6
 THE MINIMUM IS 19" TO THE DISPENSER. PLEASE SHOW
 COMPLIANCE.
  
 4. ALL PLUMBING SHEETS. THE PRINTED NAME OF THE
 ENGINEER AND THE ENGINEER'S LICENSE NUMBER SHALL BE
 LEGIBLY INDICATED ON EACH SHEET. FAC 61G15-23.002(2).
 ALSO THE SIGNATURE OF THE ENGINEER IS REQUIRED ON ALL
 SHEETS. IT APPEARS THAT INITALS HAVE BEEN USED TO SIGN
 THE PLANS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE ENGINEER SHALL BE
 SUBMITTED FOR OUR FILES.
  
 5. SHT P02.2 DOMESTIC WATER PIPING ISOMETRIC RISER
 DIAGRAM SHOWS WATER HAMMER ARRESTORS AT THE TOP OF THE
 DROPS, IN THE CEILING. PER PDI-WH 201 THE WATER HAMMER
 ARRESTORS, IF INSTALLED, SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE", NOT IN THE CEILING
 AS SHOWN. PLEASE SHOW THE WATER HAMMER ARRESTORS NEAR
 THE FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved