Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-12 16:06:37REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR OR VENTILATION CALCULATIONS COULD NOT BE
 FOUND ON PLANS. THE MINIMUM VENTILATION RATE OF
 REQUIRED OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE
 WITH SECTION 403.3. PROVIDE CALCULATIONS SHOWING
 OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, VENTILATION
 RATE REQUIRED AND VENTILATION PROVIDED FOR EACH SPACE
 WITHIN THE PROPOSED WORK AREA IN ACCORDANCE WITH FBCM
 TABLE 403.3.
  
 2. AHU SCHEDULE INDICATES THAT OUTSIDE AIR IS BEING
 PROVIDED. ONCE VENTILATION RATES HAVE BEEN VERIFIED IN
 RELATION TO COMMENT #1, PLEASE VERIFY THAT SUPPLY,
 RETURN AND EXHAUST SYSTEMS ARE IN BALANCE. THE AMOUNT
 OF SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE
 AMOUNT OF RETURN AND EXHAUST AIR IN ACCORDANCE WITH
 FBCM 403.1. IN OTHER WORDS, FOR THE SYSTEM TO BE
 BALANCED THE SUPPLY SHOULD BE APPROXIMATELY EQUAL TO
 THE RETURN MINUS THE EXHAUST PLUS THE OUTSIDE AIR, WITH
 A SLIGHT DIFFERENCE TO THE POSITIVE TO BE IN COMPLIANCE
 WITH THIS SECTION AND FBCB 13-409.1.ABC.2. EXAMPLE: AHU
 2 ON FLOOR PLAN CALLS FOR 4410 CFM SUPPLY AND 4165 CFM
 RETURN. THAT LEAVES A DIFFERENCE OF 235 CFM. THE AHU
 SCHEDULE CALLS FOR 1371 CFM OF OUTSIDE AIR. IT?S NOT
 POSSIBLE TO INTRODUCE MORE OUTSIDE AIR THAN THE
 DIFFERENCE BETWEEN THE SUPPLY AND RETURN(IN THIS CASE
 235 CFM). PLEASE CORRECT AIR BALANCES, KEEPING IN MIND
 THE REQUIRED VENTILATION RATES RELATED TO COMMENT #1.
  
 3. SHUTOFF DAMPER CONTROLS ARE REQUIRED IN ACCORDANCE
 WITH FBCB 13-409.1.ABC.3.3. BOTH OUTDOOR AIR SUPPLY AND
 EXHAUST SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS
 OR SPACES SERVED ARE NOT IN USE. GRAVITY
 (NON-MOTORIZED) DAMPERS ARE ACCEPTABLE IN BUILDING
 EXHAUST AIR SYSTEMS IN ACCORDANCE WITH EXCEPTION #1 OF
 THIS SECTION. IT IS ACKNOWLEDGED THAT MOTORIZED DAMPERS
 ARE CALLED FOR IN THE AHU SEQUENCE ON PG M04.1, BUT
 THESE DAMPERS ARE NOT SHOWN ON PLANS. PLEASE CORRECT.
  
 4.EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET
 IN ACCORDANCE WITH FAC 61G15-23.002(2). THE FULL LEGAL
 SIGNATURE OF THE DESIGNER OF RECORD SHOULD ALSO BE
 USED. THESE PLANS APPEAR TO HAVE BEEN SIGNED WITH AN
 INITIAL. PLEASE VERIFY THAT THIS IS THE DESIGNER'S FULL
 SIGNATURE PRIOR TO RESUBMITTAL. SEE SIMILAR COMMENTS
 FROM OTHER TRADES.
  
  