Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-20 18:49:08*****DENIED*****
  
  
 1.THE CODES LISTED ON COVER SHEET ARE INCORRECT;
 REFERENCE SHOULD BE AS FOLLOWS:*FIRE ALARM - 2002
 NFPA 72,*LIFE SAFETY - 2003 NFPA 101, *SPRINKLER -
 2002 NFPA 13
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE/HINDER ACCESS
 TO AND (OR) EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRELANES, ETC).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, SHOW/DISPLAY THE SUITE NUMBER
 FOR THIS TENANT SPACE.AS PER WEST PALM BEACH CODE,
 SUITE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 6.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALL
 AND CEILINGS IN TERMS OF CLASS A OR CLASS B.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT IS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW