Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-08 23:40:432008-03-08 23:40:43
  
 ** DENIED REVIEW **
  
 *** PLEASE KNOW THAT SUBMITTED DOCUMENTS ARE NOT
 COMPLETE AT THIS TIME.
  
 1) NOTE: PLEASE SEE COVER SHEET A0.00 WHICH STATES
 NFPA-70 2005 AS THE SPRINKLER CODE WHEN NFPA-70 IS THE
 NATIONAL ELECTRICAL CODE. PLEASE SEE THIS SAME COVER
 SHEET STATES NFPA-101 2003 ALSO AS THE SPRINKLER CODE
 WHICH IS ALSO NOT POSSIBLE. THE 2003 NFPA-101 IS THE
 LIFE SAFETY CODE.
 PLEASE ADJUST ON COVER SHEET AND IN PLANS AS NEEDED.
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE STATED
 ON ELECTRICAL PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE FLA-COM ENERGY CALCULATIONS
 SUBMITTED WHICH DO NOT CONTAIN ANY INPUT DATA REPORT.
 PLEASE SEE SHEET WHICH SPECIFICALLY STATES THE IDR MUST
 BE SUBMITTED. A REVIEW OF COORDINATION WITH THE ACTUAL
 ITEMS ON PLANS CAN NOT BE DONE AT THIS TIME WITHOUT
 THESE SHEETS.
 PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH
 THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3.
 PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER
 SPECIALTY LIGHTING SYSTEMS)
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH
 RESPECT TO THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES
 AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE
 SIGNATURE FROM THE OWNER AGENT.
 FS 471.025, FBC 13-103.1.1.1
  
 3) NOTE: PLEASE SEE MISSING PRINTED NAME AND PRINTED
 LICENSE NUMBER IS LISTED ON TITLE BLOCKS AS REQUIRED
 PER FAC 61G15-23.002
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS
 WHETHER OR NOT COMMENT IS MADE BY THOSE OTHER TRADES.
 ** PLEASE KNOW FOR ANY SHEETS WHICH DO NOT NEED TO BE
 RE-PRINTED FOR COMMENTS, THIS MAY BE NEATLY PRINTED OR
 STAMPED ON TITLE BLOCKS.
  
 4) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. PLEASE PROVIDE AN ORIGINAL NOTARIZED LETTER
 FOR SIGNATURE VERIFICATION. THIS WILL BE PLACED IN
 SIGNATURE FILE FOR FUTURE REFERENCE.
 FS 471.025
  
 5) NOTE: PLEASE SEE THE UNIT AS STATED ON TITLE BLOCKS
 IS SHOWN AS *B-5* WHEN THE ACTUAL SUITE/UNIT NUMBER AT
 LOCATION IS #108. PLEASE ADJUST TITLE BLOCKS.
 ** ONCE AGAIN FOR SHEETS WHICH MAY NOT NEED TO BE
 REVISED FOR COMMENTS THIS MAY BE NEATLY PRINTED OR
 STAMPED ON THE TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION 106.5
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE
 SEE THE MINIMUM LEVELS FOR ADA COMPLIANCE FOR ALL
 STROBE DEVICES SHALL MEET 75CD MINIMUM. PLEASE SEE THE
 LEVELS FOR THE HORN/STROBES INDICATE 75CD HOWEVER ALL
 STROBES ARE SHOWN AS 15CD WHICH IS WAY BELOW MINIMUM.
 PLEASE ADJUST.
 PLEASE SEE SOUND LEVELS ALSO WHICH MAY
  
 7) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V
 SYSTEMS TO BROWN, PURPLE AND YELLOW.
 THE CITY OF WEST PALM BEACH AND ALL SURROUNDING
 JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST
 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN
 AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT
 KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT
 IN THIS JURISDICTION AS WELL KEEPING WITH THE
 ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE
 REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG
 OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC
 DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A
 LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY
 MEASURE.
 90.4.
  
 8) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00
 ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF
 1992*??
 PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES
 SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE
 CHAPTER 13.
  
 9) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING
 DEVICES DOES NOT APPLY.
  
 10) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED
 FOR LIGHTING CONTROL SYSTEM.
 PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED.
 FOR EXAMPLE REAR ENTRANCE. OCCUPANT IS REQUIRED TO
 VISUALLY SEE THE LIGHTING BEING CONTROLLED OR MEETING
 THE EXCEPTION OF PILOT LIGHTS ETC.
 PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE
 TIMES.
 PLEASE SHOW A LAYOUT OF ZONES REQUIRED.
 ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING
 COMPLIANCE CAN NOT BE DONE.SEE NOTE ABOVE #2
  
 12) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC).
 PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS
 REFLECT 220.12)
  
 13) NOTE: PLEASE KNOW DEPENDING ON THE STRUCTURAL SCOPE
 OF WORK, THREE SETS OF PLANS MAY BE REQUIRED AS THIS IS
 A THRESHOLD BUILDING. THIS IS ONLY NOTED ONLY FOR
 INFORMATION.
  
 14) NOTE: PLEASE VERIFY BUS RATING OF PANELS A, B AND C
 AS THESE ARE SHOWN AS 100A YET 42CIR PANELS. 110.3,
 90.7.
 SUBMIT SPEC SHEET.
 FBC 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]