2008-03-21 07:36:54 | BUILDING PLAN REVIEW |
| PERMIT: 08020069 |
| ADD: 700 S ROSEMARY AV# 108 |
| CONT: RCC ASSOCIATES INC |
| TEL: (954)429-3700 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. |
| IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D) FL S. S. 713.13NOTICE OF COMMENCEMENT, TO BE |
| FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF |
| THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 2) ARCHITECT CHRIS DOERSCHLAG IS MISSING THE FOLLOWING |
| INFORMATION IN THE TITLE BLOCK. |
| 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A |
| REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| MUST: |
| - STATE THE FIRM NAME, ADDRESS AND TELEPHONE |
| NUMBER |
| - STATE THE FIRM LICENSE NUMBER |
| XX - STATE PROJECT NAME OR IDENTIFICATION SUITE NUMBER |
| - STATE DATE PREPARED |
| XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL - |
| INCLUDE THE PRINTED NAME OF THE |
| ARCHITECT & SEAL NUMBER SEALING THE PLANS. |
| |
| 3)SHEET A00.3 CODE SYNOPSIS PLEASE CORRECT THE |
| CORRELATION FROM THE 2001 FBC TYPE |
| II SPRINKLED FROM 2004 FBC TYPE II-A TO 2004 FBC TYPE |
| I-B, SEE CODE COMMENTARY |
| FIGURE 600. |
| |
| 4) SHEET A00.3 KEY NOTES REFERS TO THE SSMA (STEEL STUD |
| MANUFACTURERS ASSOCIATION) |
| AS THE REFERENCEDSTANDARD. PLEASE SEE TABLE 2508.1 |
| STEEL FRAMING FOR GYPSUM BOARD. |
| ASTM C 754 FOR NON-LOAD BEARING WALLS 5.3.1.2/ NOTE 1 |
| REFERS TO APPENDIX X1. |
| ASTM C 1007 FOR LOAD BEARING WALLS. |
| GA -216 |
| |
| 5)A01.1 DEMOLITION NOTE 15 IS STRUCK THROUGH |
| APPEARING TO REMOVE IT FROM THE SCOPE OF WORK, BUT |
| A02.1 INDICATES A NEW DOORWAY AND RATED WALLS. |
| DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION, |
| 106.1.2. PROVIDE RATING OF DOOR AND WALL. |
| |
| 6) A01.1 DEMOLITION NOTE 23 INDICATES TWO DOORS ARE TO |
| BE WELDED SHUT, PLEASE SEE NFPA 80- 5.2.4 (3)DOOR , |
| FRAME HINGES, HARDWARE AND NONCOMBUSTIBLE THRESHOLD ARE |
| SECURED, ALIGNED AND IN WORKING ORDER WITH NO VISIBLE |
| SIGNS OF DAMAGE. |
| |
| |
| NFPA 80- 5.2.4.2 (10) NO FIELD MODIFICATIONS TO THE |
| DOOR ASSEMBLY HAVE BEEN PREFORMED THAT VOID THE LABEL. |
| |
| 7)SHEET S04.1 DETAIL C,D & LPLEASE PROVIDE |
| ADDITIONAL INFORMATION ON THE FLOOR SHEATHING PRODUCT |
| CONCRETE BONDED PARTICLE BOARD, PROVIDE THE THICKNESS |
| OF THE PRODUCT SPAN RATINGS AND FIRE RATING IS THIS |
| PRODUCT FIRE RETARDANT TREATED, ADDITIONAL INFORMATION |
| REQUIRED 106.1.2. |
| |
| 8) SHEET S04.1 PROVIDE COMPUTATIONS WITH AN AFFIDAVIT |
| FROM THE ARCHITECT OR ENGINEER STATING THE SAFE |
| ALLOWABLE FLOOR LOAD ON EACH FLOOR (DECK ABOVE |
| RESTROOMS) IN POUNDS PER SQUARE FOOT UNIFORMLY |
| DISTRIBUTED. 110.4.2. |
| |
| 110.4.3 SIGN REQUIRED, IN EVERY BUILDING OR PART OF |
| BUILDING USED FOR STORAGE THE SAFE FLOOR LOADS AS |
| REVIEWED BY THE BUILDING OFFICIAL ON THE PLANS, SHALL |
| BE MARKED ON PLATES OF APPROVED DESIGN WHICH SHALL BE |
| SUPPLIED AND SECURELY AFFIXED BY THE OWNER OF THE |
| BUILDING IN A CONSPICUOUS PLACE IN EVERY STORY WHICH IT |
| RELATES. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |