Plan Review Notes
Plan Review Notes For Permit 08030069
Permit Number 08030069
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-21 07:36:54BUILDING PLAN REVIEW
 PERMIT: 08020069
 ADD: 700 S ROSEMARY AV# 108
 CONT: RCC ASSOCIATES INC
 TEL: (954)429-3700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S. S. 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) ARCHITECT CHRIS DOERSCHLAG IS MISSING THE FOLLOWING
 INFORMATION IN THE TITLE BLOCK.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME OR IDENTIFICATION SUITE NUMBER
 - STATE DATE PREPARED
 XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL -
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT & SEAL NUMBER SEALING THE PLANS.
  
 3)SHEET A00.3 CODE SYNOPSIS PLEASE CORRECT THE
 CORRELATION FROM THE 2001 FBC TYPE
 II SPRINKLED FROM 2004 FBC TYPE II-A TO 2004 FBC TYPE
 I-B, SEE CODE COMMENTARY
 FIGURE 600.
  
 4) SHEET A00.3 KEY NOTES REFERS TO THE SSMA (STEEL STUD
 MANUFACTURERS ASSOCIATION)
 AS THE REFERENCEDSTANDARD. PLEASE SEE TABLE 2508.1
 STEEL FRAMING FOR GYPSUM BOARD.
 ASTM C 754 FOR NON-LOAD BEARING WALLS 5.3.1.2/ NOTE 1
 REFERS TO APPENDIX X1.
 ASTM C 1007 FOR LOAD BEARING WALLS.
 GA -216
  
 5)A01.1 DEMOLITION NOTE 15 IS STRUCK THROUGH
 APPEARING TO REMOVE IT FROM THE SCOPE OF WORK, BUT
 A02.1 INDICATES A NEW DOORWAY AND RATED WALLS.
 DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION,
 106.1.2. PROVIDE RATING OF DOOR AND WALL.
  
 6) A01.1 DEMOLITION NOTE 23 INDICATES TWO DOORS ARE TO
 BE WELDED SHUT, PLEASE SEE NFPA 80- 5.2.4 (3)DOOR ,
 FRAME HINGES, HARDWARE AND NONCOMBUSTIBLE THRESHOLD ARE
 SECURED, ALIGNED AND IN WORKING ORDER WITH NO VISIBLE
 SIGNS OF DAMAGE.
  
  
 NFPA 80- 5.2.4.2 (10) NO FIELD MODIFICATIONS TO THE
 DOOR ASSEMBLY HAVE BEEN PREFORMED THAT VOID THE LABEL.
  
 7)SHEET S04.1 DETAIL C,D & LPLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE FLOOR SHEATHING PRODUCT
 CONCRETE BONDED PARTICLE BOARD, PROVIDE THE THICKNESS
 OF THE PRODUCT SPAN RATINGS AND FIRE RATING IS THIS
 PRODUCT FIRE RETARDANT TREATED, ADDITIONAL INFORMATION
 REQUIRED 106.1.2.
  
 8) SHEET S04.1 PROVIDE COMPUTATIONS WITH AN AFFIDAVIT
 FROM THE ARCHITECT OR ENGINEER STATING THE SAFE
 ALLOWABLE FLOOR LOAD ON EACH FLOOR (DECK ABOVE
 RESTROOMS) IN POUNDS PER SQUARE FOOT UNIFORMLY
 DISTRIBUTED. 110.4.2.
  
 110.4.3 SIGN REQUIRED, IN EVERY BUILDING OR PART OF
 BUILDING USED FOR STORAGE THE SAFE FLOOR LOADS AS
 REVIEWED BY THE BUILDING OFFICIAL ON THE PLANS, SHALL
 BE MARKED ON PLATES OF APPROVED DESIGN WHICH SHALL BE
 SUPPLIED AND SECURELY AFFIXED BY THE OWNER OF THE
 BUILDING IN A CONSPICUOUS PLACE IN EVERY STORY WHICH IT
 RELATES.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  