Plan Review Notes
Plan Review Notes For Permit 08030068
Permit Number 08030068
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-21 14:52:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1,FLORIDA STATUTES 2007, AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECT'S SIGNATURE IS A PHOTOCOPY. WHEN
 SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1) (A) FLORIDA STATUTES. THE ARCHITECTURAL
 FIRM, WHOSE TITLE BLOCK APPEARS ON THE PLANS, MUST SIGN
 AND SEAL THE PLAN PER 481.221(1) (B) FS.
  
 2} AS STATED IN THE PREVIOUS FIRE REVIEW, THE
 APPLICATION INDICATES THIS WORK ON THE 18TH FLOOR, BUT
 THE PLANS ARE LABELED 15TH AND 16TH FLOOR, CORRECT THE
 ADDRESS ON THE PLANS.
  
 NOTE: UNLESS THE CONTRACTOR GOES TO THE ARCHITECT OF
 RECORD, HE MAY NEED TO DRAW HIS OWN PLANS, PRINT AND
 SIGN HIS NAME AS THE DESIGNER OF RECORD, PERMISSIBLE
 PER 471.003 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718