Plan Review Notes For Permit 08030068 |
Permit Number |
08030068 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-11 16:42:54 | *****DENIED***** | | | | | | 1.ONLY ONE PLAN SET WAS SUBMITTED FOR REVIEW.PLEASE | | BE ADVISED THAT AT LEAST TWO NO MORE THAN THREE | | CONSTRUCTION DOCUMENTS, SPECIFICATIONS, AND OTHER DATA | | SHALL BE SUBMITTED WITH EACH APPLICATION FOR A PERMIT. | | | | 2.THE PERMIT APPLICATION AND WHAT IS REGISTERING IN | | OUR PERMITTING SYSTEM REFERENCES SUITE 1800, HOWEVER, | | THE 15TH AND 16TH FLOOR ARE LISTED AS THE SCOPE OF WORK | | SITE. | | | | 3.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE | | EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA IN NFPA 101, | | 2003 EDITION, 7.2.1.6.2 ARE MET. | | | | 4.SHOW THE MARKED EXIT DOORS ON THE FLOOR PLAN. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING ON THE PLAN WHERE EACH ITEM HAS BEEN | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|