 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENT AS PREVIOUS REVIEW:
  
 1} 13-415.2.ABC.1.3 EXTERIOR BUILDING LIGHTING POWER.
 THE TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL
 EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE
 INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE
 415.2.ABC.1.3 FOR THESE APPLICATIONS, PLUS AN
 ADDITIONAL UNRESTRICTED ALLOWANCE OF 5 PERCENT OF THAT
 SUM. TRADE-OFFS ARE ALLOWED ONLY AMONG EXTERIOR
 LIGHTING APPLICATIONS LISTED IN THE TABLE
 13-415.2.ABC.1.3, "TRADABLE SURFACES" SECTION. EXTERIOR
 LIGHTING FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN
 THE EXCEPTIONS TO SECTIONS 415.0 AND 415.2.ABC.1.3)
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 415.1.ABC.2.* PHOTOMETRICS IS NOT LIGHTING POWER
 DENSITIES, PLEASE SEE THE SECTION SITED.
  
 NEW COMMENT:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. THE WIND LOAD ANALYSIS SIGNATURE IS A PHOTOCOPY.
  
 2} 13-415.1.ABC.1.4 EXTERIOR LIGHTING CONTROL.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 415.0 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE, OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ASTRONOMICAL
 TIME SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING
 AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD
 OF AT LEAST 10 HOURS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  