| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| SAME COMMENT AS PREVIOUS REVIEW: |
| |
| 1} 13-415.2.ABC.1.3 EXTERIOR BUILDING LIGHTING POWER. |
| THE TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL |
| EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE |
| INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE |
| 415.2.ABC.1.3 FOR THESE APPLICATIONS, PLUS AN |
| ADDITIONAL UNRESTRICTED ALLOWANCE OF 5 PERCENT OF THAT |
| SUM. TRADE-OFFS ARE ALLOWED ONLY AMONG EXTERIOR |
| LIGHTING APPLICATIONS LISTED IN THE TABLE |
| 13-415.2.ABC.1.3, "TRADABLE SURFACES" SECTION. EXTERIOR |
| LIGHTING FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN |
| THE EXCEPTIONS TO SECTIONS 415.0 AND 415.2.ABC.1.3) |
| SHALL COMPLY WITH THE REQUIREMENTS OF SECTION |
| 415.1.ABC.2.* PHOTOMETRICS IS NOT LIGHTING POWER |
| DENSITIES, PLEASE SEE THE SECTION SITED. |
| |
| NEW COMMENT: |
| |
| 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK |
| MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 |
| FAC. THE WIND LOAD ANALYSIS SIGNATURE IS A PHOTOCOPY. |
| |
| 2} 13-415.1.ABC.1.4 EXTERIOR LIGHTING CONTROL. |
| LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| SECTION 415.0 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| IS AVAILABLE, OR WHEN THE LIGHTING IS NOT REQUIRED |
| DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN |
| ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR |
| DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN |
| ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ASTRONOMICAL |
| TIME SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING |
| AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD |
| OF AT LEAST 10 HOURS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |