Plan Review Notes
Plan Review Notes For Permit 08030031
Permit Number 08030031
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-05 12:37:262004 FBC W/2007 REVISIONS
 ROOF OVER
  
 DENIED BY BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE LISTED IN THE PRODUCT
 APPROVAL IS TOO LOW FOR THE CORNER AND PERIMETER AREAS.
 SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING FROM
 A FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED
 ROOF CONSULTANT. SEE LIMITATION NUMBER 7 ON PAGE 30 OF
 THE NOA.
  
 2) THE ROOF WILL BE REQUIRED TO HAVE A PRE-INSPECTION
 PERFORMED BY THE CITY BUILDING DEPARTMENT.
  
 3) A RECORDED COPY OF THE NOC WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]