Plan Review Notes
Plan Review Notes For Permit 08030012
Permit Number 08030012
Review Stop G
Sequence Number 3
Notes
Date Text
2008-07-25 16:01:22REVISION: "OK" RELOCATED MP REGULATOR WITH ADDED PIPING
 TO 0.5 PSI SYSTEM AND LOOPED 8' OF 3/4" PE PIPING FROM
 POOL HEATER TO MP REGULATORS NEW LOCATION.
  
 ****************PROVISO****************
 PER FBC, FUEL GAS, SECTION 409.4 MP REGULATOR VALVES:
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER