Plan Review Notes For Permit 08020712 |
Permit Number |
08020712 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-04 14:11:19 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE FEEDER CONDUITS FROM THE MAIN DISCONNECT TO THE | | JUNCTION BOX THAT IS PROPOSED TO REPLACE THE 600 AMP | | PANEL ARE NOT SIZED ON THE RISER, SHEET E.3. THE NOTE | | "2 SETS OF 250 MCM. CU" IS ALSO NOT CLEAR AS THE SIZE | | AND NUMBER OF CONDUITS IS NOT NOTED. THEREFORE BOX FILL | | PER 314.28 CANNOT BE REVIEWED. IT WOULD APPEAR THE | | 12"X12" BOX IS NOT IN COMPLIANCE WITH EVEN THE 21/2" | | CONDUIT FEEDING PANEL "A". CLARIFY SIZES. | | | | 2} THE 2/0 FEEDERS FROM THE JUNCTION BOX TO PANEL "A" | | DO NOT COMPLY WITH THE AMPERAGE RATING OF 225 PER | | 310.16.THEY WOULD NEED TO BE 4/0 CU MINIMUM FOR 225 | | AMPS. | | | | 3} THE FEED FROM PANEL "A" TO PANEL "B", SAME COMMENT | | AS ABOVE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | | | | | |
|