Plan Review Notes
Plan Review Notes For Permit 08020712
Permit Number 08020712
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-04 14:11:19 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FEEDER CONDUITS FROM THE MAIN DISCONNECT TO THE
 JUNCTION BOX THAT IS PROPOSED TO REPLACE THE 600 AMP
 PANEL ARE NOT SIZED ON THE RISER, SHEET E.3. THE NOTE
 "2 SETS OF 250 MCM. CU" IS ALSO NOT CLEAR AS THE SIZE
 AND NUMBER OF CONDUITS IS NOT NOTED. THEREFORE BOX FILL
 PER 314.28 CANNOT BE REVIEWED. IT WOULD APPEAR THE
 12"X12" BOX IS NOT IN COMPLIANCE WITH EVEN THE 21/2"
 CONDUIT FEEDING PANEL "A". CLARIFY SIZES.
  
 2} THE 2/0 FEEDERS FROM THE JUNCTION BOX TO PANEL "A"
 DO NOT COMPLY WITH THE AMPERAGE RATING OF 225 PER
 310.16.THEY WOULD NEED TO BE 4/0 CU MINIMUM FOR 225
 AMPS.
  
 3} THE FEED FROM PANEL "A" TO PANEL "B", SAME COMMENT
 AS ABOVE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  