Plan Review Notes
Plan Review Notes For Permit 08020693
Permit Number 08020693
Review Stop E
Sequence Number 5
Notes
Date Text
2008-12-05 09:05:16** PROVISO**
  
  
  
 1) NOTE: WATER HEATER LOAD IN AMPERAGE NOT SHOWN
 CORRECTLY. LOAD IS ALSO A CONTINUOUS LOAD UNDER 2005
 NEC 422.13.
  
 REVISE CALCULATIONS AND LOADS ALONG ON WATER HEATER.
 THIS WILL BE NEEDED ALONG WITH ANY OTHER REVISIONS MADE
 TO PLANS.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  