Plan Review Notes
Plan Review Notes For Permit 08020693
Permit Number 08020693
Review Stop P
Sequence Number 3
Notes
Date Text
2008-10-29 07:20:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS
 REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS
 EXPIRED.
  
 1. OK
  
 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES.
 SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE
 STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE
 REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER
 RISER DIAGRAMS.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SERVICE SINKS WERE NOT
 ADDRESSED.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) WAS
 NOT ADDRESSED. ALSO SHOW THE CLEAR FLOOR SPACE REQUIRED
 FOR THE DRINKING FOUNTAINS PER SECTION 11-4.15.5.
  
 4. OK
  
 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19,
 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR
 THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF
 ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW
 COMPLIANCE.
 ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE
 COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW
 COMPLIANCE FOR THE FOLLOWING:
 ___FOR SHOWER
 A. 11-4.21.4 GRAB BARS
 B. 11-4.21.5 CONTROLS
 C. 11-4.21.6 SHOWER UNIT
 ******RESPONSE NOTED, BUT THE W/C SHALL BE 18" OFF THE
 WALL. MY MISTAKE ON THE SPACING FOR THE WATER CLOSET. A
 MINIMUM 36" IS REQUIRED FROM THE WALL TO THE LAV. SEE
 FIGURE 28. THERE IS A NOTE STATING "BATH TO BE HANDICAP
 ADAPTABLE". THIS IS NOT CORRECT. PER SECTION
 11-4.1.3(11), IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. PLEASE DELETE NOTE AND MAKE THE
 BATHROOM ACCESSIBLE. SHOW THE GRAB BARS FOR THE W/C.
  
 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE
 BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE
 SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE.
 FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE
 REQUIRED FOR THE SINK SHALL BE SHOWN ON THE FLOOR PLAN.
 SECTION 11-4.24.5. FORWARD APPROACH REQUIRED MAXIMUM
 19" UNDERNEATH THE SINK.
  
 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD ON DETAIL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RELIEF VALVE, (P&T),
 SHALL NOT BE USED AS A MEANS OF CONTROLLING THERMAL
 EXPANSION. SECTION 504.4. PLEASE INDICATE METHOD OF
 CONTROL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ******NO RESPONSE, ONE SET OF VOIDED SHEETS HAS NOT
 BEEN SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved