Date |
Text |
2008-10-29 07:20:51 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| ******FROM PREVIOUS REVIEWS: |
| |
| A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS |
| REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS |
| EXPIRED. |
| |
| 1. OK |
| |
| 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES. |
| SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE |
| STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE |
| REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER |
| RISER DIAGRAMS. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE SERVICE SINKS WERE NOT |
| ADDRESSED. |
| |
| 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS |
| WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) WAS |
| NOT ADDRESSED. ALSO SHOW THE CLEAR FLOOR SPACE REQUIRED |
| FOR THE DRINKING FOUNTAINS PER SECTION 11-4.15.5. |
| |
| 4. OK |
| |
| 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS |
| SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, |
| 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR |
| THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF |
| ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW |
| COMPLIANCE. |
| ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE |
| COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW |
| COMPLIANCE FOR THE FOLLOWING: |
| ___FOR SHOWER |
| A. 11-4.21.4 GRAB BARS |
| B. 11-4.21.5 CONTROLS |
| C. 11-4.21.6 SHOWER UNIT |
| ******RESPONSE NOTED, BUT THE W/C SHALL BE 18" OFF THE |
| WALL. MY MISTAKE ON THE SPACING FOR THE WATER CLOSET. A |
| MINIMUM 36" IS REQUIRED FROM THE WALL TO THE LAV. SEE |
| FIGURE 28. THERE IS A NOTE STATING "BATH TO BE HANDICAP |
| ADAPTABLE". THIS IS NOT CORRECT. PER SECTION |
| 11-4.1.3(11), IF BATHING ROOMS ARE PROVIDED, THEN EACH |
| PUBLIC AND COMMON USE BATHROOM SHALL COMPLY WITH |
| SECTION 11-4.23. PLEASE DELETE NOTE AND MAKE THE |
| BATHROOM ACCESSIBLE. SHOW THE GRAB BARS FOR THE W/C. |
| |
| 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE. |
| PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION |
| 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE |
| BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE |
| SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE. |
| FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT |
| ALLOWED IN THE CLEAR FLOOR SPACE. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE |
| REQUIRED FOR THE SINK SHALL BE SHOWN ON THE FLOOR PLAN. |
| SECTION 11-4.24.5. FORWARD APPROACH REQUIRED MAXIMUM |
| 19" UNDERNEATH THE SINK. |
| |
| 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION |
| CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE |
| INDICATE METHOD ON DETAIL. |
| ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT THE RELIEF VALVE, (P&T), |
| SHALL NOT BE USED AS A MEANS OF CONTROLLING THERMAL |
| EXPANSION. SECTION 504.4. PLEASE INDICATE METHOD OF |
| CONTROL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| ******NO RESPONSE, ONE SET OF VOIDED SHEETS HAS NOT |
| BEEN SUBMITTED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |