Plan Review Notes For Permit 08020693
Permit Number 08020693
Review Stop E
Sequence Number 3
Notes
Date Text
2008-10-30 16:55:32 
  
 ** DENIED REVIEW**
  
 ** A CALL WAS PLACED TO THE ENGINEER OF RECORD AT THE
 TIME OF THIS REVIEW HOWEVER WAS NOT IN THE OFFICE. A
 MESSAGE WAS LEFT SO THESE ITEMS BELOW COULD BE GONE
 OVER. PLANS ARE COMING BACK WITH COMMENTS FROM OTHER
 TRADES
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS CAN NOT BE
 STAMPED OR SIGNED OFF BY ELECTRICAL AS THERE ARE ERRORS
 WITH OTHER COMPONENTS TO THE BUILDING WHICH DO NOT
 COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES.
 (BUILDING)
 EXAMPLE WOULD BE THE FLOORS WHICH ARE USING CARPET AND
 RUBBER PADDING WHERE THE FINISH SCHEDULE ON THE C SHEET
 INDICATE CONCRETE, TILE, ETC
 THE IDR NEEDS TO INDICATE THE WATER HEATER SIZE WHICH
 COORDINATES WITH PLANS. SEE NEXT COMMENT FOR LOADS.
 FBC 13-400.3A
  
 2) NOTE: PLEASE SEE THE LOADS WHICH ARE SHOWN ON THE
 PANEL SCHEDULES ARE IN QUESTION. THE PANEL INDICATES
 LOADS BY *AMPS* FOR EACH PHASE HOWEVER PLEASE SEE SMALL
 APPLIANCE(S), MICROWAVE AND OTHER SIMILAR ITEMS WHICH
 ARE SHOWN AS 1.5AMPS, 1.2 AMPS ETC. IS THIS NOT KVA?
 PLEASE SEE PANEL *A* FOR EXAMPLE:
 PLEASE SEE THE LOAD FOR THE WATER HEATER WHICH STATES
 20.0AMPS PER PHASE. WHAT SIZE OF WATER HEATER IS THIS?
 PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH HAS BEEN
 REVISED TO CONSIDER STORAGE TYPE WATER HEATERS AS
 CONTINUOUS LOADS. THIS WOULD REQUIRE LOAD CALCULATIONS
 TO SHOW 125% FOR THIS UNIT.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  