2008-10-30 16:55:32 | |
| |
| ** DENIED REVIEW** |
| |
| ** A CALL WAS PLACED TO THE ENGINEER OF RECORD AT THE |
| TIME OF THIS REVIEW HOWEVER WAS NOT IN THE OFFICE. A |
| MESSAGE WAS LEFT SO THESE ITEMS BELOW COULD BE GONE |
| OVER. PLANS ARE COMING BACK WITH COMMENTS FROM OTHER |
| TRADES |
| |
| 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS CAN NOT BE |
| STAMPED OR SIGNED OFF BY ELECTRICAL AS THERE ARE ERRORS |
| WITH OTHER COMPONENTS TO THE BUILDING WHICH DO NOT |
| COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES. |
| (BUILDING) |
| EXAMPLE WOULD BE THE FLOORS WHICH ARE USING CARPET AND |
| RUBBER PADDING WHERE THE FINISH SCHEDULE ON THE C SHEET |
| INDICATE CONCRETE, TILE, ETC |
| THE IDR NEEDS TO INDICATE THE WATER HEATER SIZE WHICH |
| COORDINATES WITH PLANS. SEE NEXT COMMENT FOR LOADS. |
| FBC 13-400.3A |
| |
| 2) NOTE: PLEASE SEE THE LOADS WHICH ARE SHOWN ON THE |
| PANEL SCHEDULES ARE IN QUESTION. THE PANEL INDICATES |
| LOADS BY *AMPS* FOR EACH PHASE HOWEVER PLEASE SEE SMALL |
| APPLIANCE(S), MICROWAVE AND OTHER SIMILAR ITEMS WHICH |
| ARE SHOWN AS 1.5AMPS, 1.2 AMPS ETC. IS THIS NOT KVA? |
| PLEASE SEE PANEL *A* FOR EXAMPLE: |
| PLEASE SEE THE LOAD FOR THE WATER HEATER WHICH STATES |
| 20.0AMPS PER PHASE. WHAT SIZE OF WATER HEATER IS THIS? |
| PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH HAS BEEN |
| REVISED TO CONSIDER STORAGE TYPE WATER HEATERS AS |
| CONTINUOUS LOADS. THIS WOULD REQUIRE LOAD CALCULATIONS |
| TO SHOW 125% FOR THIS UNIT. |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |