2008-11-19 08:54:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-5.) ADDRESSED.
  
 6.) PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. TWO
 ORIGINALS REQUIRED.
  
 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002,
 ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON
 A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
 THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES.
  
 3RD REVIEW, CERTIFICATE OF AUTHORIZATION NOT INCLUDED
 ON THE REPORT AND SIGNATURE IS A PHOTOCOPY,
 FAC61G15-23.002.
  
 7.) ADDRESSED.
  
 8.) PARKING STRIPING IS TO COMPLY WITH CITY OF WEST
 PALM BEACH STANDARD, SEE ATTACHED DETAIL. REVISE C1.
  
 ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL
 ADDRESS. AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS
 ACCESSIBLE PARKING. THEREFORE, IT APPEARS THAT THE SITE
 PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE
 COMPLIANCE.
  
 SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE
 PLAN ON THE SAME PAGE. THE SITE PLAN SHOWS A WHEEL
 STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG.
 COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL
 NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE.
  
 SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF
 THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE
 FRONT ENTRY), FBC11-4.6.2(1).
  
 3RD REVIEW, SIDEWALK WIDTH NOT INDICATED
 FBC11-4.6.2(1). STRIPING DETAIL NOT IN COMPLIANCE WITH
 CITY STANDARDS.
  
 9-22.) ADDRESSED.
  
 23.) FROM FIRST LIST; COMMENT NOT ADDRESSED. SHOW THE
 SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE
 PARKING AND THE BUILDING. C1 SHOWS A 44INCH SIDEWALK,
 WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE
 ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS. THE
 LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE
 SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE
 IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE
 PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE
 1. THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN
 SHOWS A WHEEL STOP. SEE FBC11-4.6.3, VEHICLE OVERHANGS
 CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT
 CLEAR.
  
 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN,
 RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY
 CONTRACTOR. PLEASE REVISE SITE PLAN TO SHOW CODE
 COMPLIANCE.
  
 3RD REVIEW, CIVIL SHEETS SUBMITTED AND OTHER SITE PLANS
 PREVIOUSLY SUBMITTED REMOVED. THE NEW SHEETS DO NOT
 SHOW THE SIDEWALK WIDTH, FBC11-4.6.2(1), SEE ALSO
 COMMENT 8.
  
 24-29.) ADDRESSED.
  
 30.) THE PREVIOUS LISTS STATED THAT THE SHOWER BATHROOM
 MUST BE ACCESSIBLE, NOT ADAPTABLE. THE PLANS HAVE BEEN
 REVISED TO MAKE THIS ROOM ACCESSIBLE, BUT THE NOTE
 STATING THIS IS ADAPTABLE IS STILL ON THE PLAN. PLEASE
 REVISE TO REMOVE THIS NOTE.
  
 31.) PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB
 BARS, MIRRORS, FBC 11.
  
 2ND REVIEW, SEE PLUMBING COMMENTS.
  
 3RD REVIEW, THE W/C IS SHOWN AS 1'4" FROM WALL, 18"
 REQUIRED, FBC11-4.16.2. PLEASE REVISE.
  
 32-39.) ADDRESSED.
  
 40.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
 PLEASE SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT
 GLASS AND FRONT DOOR. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FBC*106.
  
 41.) FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3. THIS CAN
 BE DONE AT THE TIME OF ROOF PERMIT APPLICATION.
  
 THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM
 THE PACKAGE. THIS IS REQUIRED, REVIEWED BY DESIGNER OF
 RECORD. OTHER INFORMATION (ASSEMBLY, ENHANCED
 FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT.
  
 42.) SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ.
 PLEASE PROVIDE LEGIBLE COPIES. THEY MAY BE AVAILABLE AT
 WWW.BUILDINGCODEONLINE.COM.
  
 PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL. IT IS
 ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES.
 PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH
 PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE
 DOCUMENTS FOR THAT PRODUCT. THIS IS AVAILABLE AT
 WWW.FLORIDABUILDING.ORG
  
 3RD REVIEW, THE GARAGE DOOR PRODUCT APPROVAL HAS A
 DESIGN PRESSURE LIMITATION OF +-30PSF. +33.7/-36.7
 REQUIRED, SEE PAGE A3.
  
 43.) ADDRESSED.
  
 44-45.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
  
 46-51.) ADDRESSED.